4 Comparison of Performance Specifications
4.2 Analog Output
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
Common Items
A
Common Items
B
FX
3U
-4AD
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3G
-2AD-BD
E
FX
3U
-4DA
F
FX
3U
-4DA-ADP
G
FX
3G
-1DA-BD
H
FX
3U
-3A-ADP
I
FX
3U
-4AD-PT
-ADP
J
FX
3U
-4AD-PTW
-ADP
4.2 Analog Output
4.2.1 FX3U-4DA-ADP
Specifications FX3U-4DA-ADP
Voltage output Current output
Number of output points 4ch
Analog output range 0V to 10V DC
(External load: 5k to 1MΩ)
4mA to 20mA DC
(External load: 500Ω or less)
Offset Impossible to change Impossible to change
Gain
Digital input 12 bits, binary
Resolution 2.5mV(10V×1/4000) 4μA(16mA×1/4000)
Overall accuracy
Ambient temperature:
25±5°C±0.5%(±50mV) for 10V full scale ±0.5%(±80μA) for 16mA full scale
Ambient temperature:
0 to 55°C±1.0%(±100mV) for 10V full scale ±1.0%(±160μA) for 16mA full scale
Reference
If the external load resistance (Rs) is less than
5kΩ, the accuracy increases as shown in the
following formula: (Increase: 100 mV per 1%) -
Time required for D/A
conversion
•FX
3U/FX3UC Series PLC : 200μs (Data updated every scan time.)
•FX
3G Series PLC : 250μs (Data updated every scan time.)
Output characteristics
Insulation method
The photocoupler is used to insulate the analog output area from the PLC.
The DC/DC converter is used to insulate the power supply from the analog inputs.
Channels are not insulated from each other.
Number of I/O points
occupied 0 point (This number is not related to the maximum I/O points of the PLC.)
47
×
100
Rs+47 -0.9(%)
0
10V
4000
Digital input
Analog output
4080
0
20mA
4000
Digital input
Analog output
4mA
4080