14 - 46
14. OPTIONS AND AUXILIARY EQUIPMENT
(2) Selection example
Indicated below is an example of selecting a leakage current breaker under the following condi tions.
M
Servo
amplifier
MR-J2S-60CP HC-MFS73
2mm2 5m(196.85inch)
Ig1 Ig2
Iga Igm
NV
2mm2 5m(196.85inch)
Use a leakage current breaker designed for suppressing harmonics/surges .
Find the terms of Equation (14.1) f rom the diagram.
Ig1 20 1000
50.1 [mA]
Ig2 20 1000
50.1 [mA]
Ign 0 (not used)
Iga 0.1 [mA]
Igm 0.1 [mA]
Insert these values in Equation (14.1).
Ig 10 {0.1 00.1 1(0.1 0.1)}
4 [mA]
According to the result of calculation, use a leakage current breaker having the rated sensitivity
current (Ig) of 4[mA] or more. A leakage current breaker having Ig of 15[mA] is used with the NV-
SP/CP/ SW/CW/HW series.