8 - 14
Table8.10 I/O assignment setting list (continued)
Item Parameter
No. Description Setting range Default Reference
Switch setting 0407H
Set various switches of an
intelligent function module.
Refer to the manual for the
intelligent function module used. Blank Section 6.10
Detailed
setting
Error time
output mode 0403H
Set whether to clear or hold the
output in case of a stop error in
the control CPU.
Clear/Hold Clear Section 6.8
H/W error
time PLC
operarion
mode
4004H
Set whether to stop or continue
the operarion of the control
CPU in case of a hardware
failure of the intelligent function
module.
Stop/Continue Stop Section 6.9
I/O response
time 0405H
Set a response time for the
input module, high-speed input
module, I/O combined module,
or interrupt module.
•I nput or I/O mix: 1ms, 5ms,
10ms, 20ms, or 70ms
•Hi input or Interrupt: 0.1ms,
0.2ms, 0.4ms, 0.6ms, or 1ms
• Input or I/O mix:
10ms
•Hi inpu t or Interrupt:
0.2ms
Section 6.7
Control PLC 0406H
Set the control CPU for the input/
output modules and intelligent
function module.
No.1, No.2, No.3, or No.4 No.1
QCPU User's
Manual (Multiple
CPU System)