12-26
2126
[SP. UNIT LAY. ERR.]
CPU module locations in a multiple CPU system
are either of the following.
•There are empty slots between the QCPU and
QCPU/motion controller.
•A module other than the High Performance
model QCPU/Process CPU (including the motion
controller) is mounted on the left-hand side of the
High Performance model QCPU/Process CPU.
■Collateral information
•Common Information:Module No. (Slot No.)
•Individual Information:–
■Diagnostic Timing
•At po wer ON/ At reset
•Mount modules on the available slots so that the
empty slots will be located on the right-hand side
of the CPU module.
•Remove the module mounted on the left-hand
side of the High Performance model QCPU/
Process CPU, and mount the High Performance
model QCPU/Process CPU on the empty slot.
Mount the motion CPU on the right-hand side of
the High Performance model QCPU/Process
CPU.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)*3
QnPH
2128
[SP.UNIT LAY ERR.]
The unusable module is mounted on the extension
base unit in the redundant system.
■Collateral information
•Common Information:Module No.
•Individual Information:–
■Diagnostic Timing
•At power-ON/ At reset
•Remove the unusable module from the extension
base unit. QnPRH*6
2150
[SP. UNIT VER. ERR.]
In a multiple CPU system, the control CPU of the
intelligent function module incompatible with the
multiple CPU system is set to other than CPU No.1.
■Collateral information
•Common Information:Module No. (Slot No.)
•Individual Information:–
■Diagnostic Timing
•At powe r ON/At reset/
At writing to progurammable controller
•Change the intelligent function module for the
one compatible with the multiple CPU system
(function version B).
•Change the setting of the control CPU of the
intelligent function module incompatible with the
multiple CPU system to CPU No.1.
Q00J/Q00/Q01
QnPH
QuU*10
2151
[SP. UNIT VER. ERR.]
Either of the following modules incompatible with
the redundant system has been mounted in a
redundant system.
•CC-Link IE controller network modules
•MELSECNET/H modules
•Eth ernet modules
■Collateral information
•Common Information:Module No. (Slot No.)
•Individual Information:–
■Diagnostic Timing
•At powe r ON/At reset/
At writing to progurammable controller
Use either of the following modules compatible with
the redundant system.
•CC-Link IE controller network modules
•MELSECNET/H modules
•Ethernet modules
QnPRH
Error
Code
(SD0)
Error Contents and Cause Corrective Action LED Status
CPU Status
Corresponding
CPU
*3 The function version is B or later.
*6 The module whose first 5 digits of serial No. is "09012" or later.