12.1 Error Code List
12.1.5 Error code list (3000 to 3999)
3102
[LINK PARA. ERROR]
•LB/LW own station send range at LB/LW4000 or
later was set.
•LB/LW setting (2) was performed.
Collateral information
•Common Information:File name/ Drive name
•Individual Information:Parameter number
Diagnostic Timing
•At p ower ON/At reset/STOP RUN
Examine the network range assignments for the
network parameter in the control station.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Q00J/Q00/Q01
3103
[LINK PARA. ERROR]
In a multiple CPU system, Ethernet interface
module under control of another station is specified
to the start I/O number of the Ethernet network
parameter.
Collateral information
•Common Information:File name/ Drive name
•Individual Information:Parameter number
Diagnostic Timing
•At p ower ON/At reset/STOP RUN
•Delete the Ethernet network parameter of
Ethernet interface module under control of
another station.
•Change the setting to the start I/O number of
Ethernet interface module under control of the
host station.
Q00/Q01*1
Qn(H)*1
QnPH
QnU*10
[LINK PARA. ERROR]
•Although the number of modules has been set to
one or greater number in the Ethernet module
count parameter setting, the number of actually
mounted module is zero.
•The start I/O No. of the Ethernet network
parameter differs from the I/O No. of the actually
mounted module.
Collateral information
•Common Information:File name/ Drive name
•Individual Information:Parameter number
Diagnostic Timing
•At p ower ON/At reset/STOP RUN
•Correct and write the network parameters.
•If the error occurs after correction, it suggests a
hardware fault. (Contact your local Mitsubishi
representative.)
QCPU
[LINK PARA. ERROR]
•Ethernet module whose network type is set to
“Ethernet (main base)” is mounted on the
extension base unit in the redundant system.
•Ethernet module whose network type is set to
“Ethernet (extension base)” is mounted on the
main base unit in the redundant system.
Collateral information
•Common Information:File name/ Drive name
•Individual Information:Parameter number
Diagnostic Timing
•At p ower ON/At reset/STOP RUN
QnPRH*7
3104
[LINK PARA. ERROR]
•The Ethernet, MELSECNET/H and
MELSECNET/10 use the same network number.
•The network number, station number or group
number set in the network parameter is out of
range.
•The specified I/O number is outside the range of
the used CPU module.
•The Ethernet-specific parameter setting is not
normal.
Collateral information
•Common Information:File name/ Drive name
•Individual Information:Parameter number
Diagnostic Timing
•At p ower ON/At reset/STOP RUN
•Correct and write the network parameters.
•If the error occurs after correction, it suggests a
hardware fault. (Contact your local Mitsubishi
representative.)
QCPU
Error
Code
(SD0)
Error Contents and Cause Corrective Action LED Status
CPU Status
Corresponding
CPU
*1 The function version is B or later.
*7 The module whose first 5 digits of serial No. is "09012" or later.
*10 The Universal model QCPU except the Q00UJCPU.