12-60
4353
[MULTI-COM.ERROR]
The device which cannot be used for the multiple
CPU high-speed transmission dedicated instruction
specified by the program is specified.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•When instruction executed
Read the common information of the error using
the peripheral device, check error step
corresponding to its numerical value (program error
location), and correct the problem.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
QnU*7
4354
[MULTI-COM.ERROR]
The character string which cannot be handled by
the multiple CPU high-speed transmission
dedicated instruction is specified.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•When instruction executed
QnU*7
4355
[MULTI-COM.ERROR]
The number of read/write data (number of request/
receive data) for the multiple CPU high-speed
transmission dedicated instruction specified by the
program is not valid.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•When instruction executed
4400
[SFCP. CODE ERROR]
No SFCP or SFCPEND instruction in SFC
program.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•STOP RUN
Write the program to the CPU module again using
GX Developer.
Qn(H)
QnPH
QnPRH
4410
[CAN'T SET(BL)]
The block number designated by the SFC program
exceeds the range.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•STOP RUN
Q00J/Q00/Q01*2
Qn(H)
QnPH
QnPRH
QnU
4411
[CAN'T SET(BL)]
Block number designations overlap in SFC
program.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•STOP RUN
4420
[CAN'T SET(S)]
A step number designated in an SFC program
exceeds the range.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•STOP RUN
Error
Code
(SD0)
Error Contents and Cause Corrective Action LED Status
CPU Status
Corresponding
CPU
*2 The function version is B or later.