12-82
9010
[<CHK>ERR ***-***]
Error detected by the CHK instruction.
Collateral information
•Common Information:Program error location
•Individual Information:Failure No.
Diagnostic Timing
•When instruction executed
Read the individual information of the error using
the peripheral device, and check the program
corresponding to the numerical value (error
number) there.
RUN:
On
ERR.:
Off
USER LED On
CPU Status:
Continue
Qn(H)
QnPH
QnPRH
9020
[BOOT OK]
Storage of data onto ROM was completed normally
in automatic write to standard ROM.
(BOOT LED also flickers.)
Collateral information
•Common Information:–
•Individual Information:–
Diagnostic Timing
•At powe r ON/At reset
Use the DIP switches to set the valid parameter
drive to the standard ROM. Then, switch power on
again, and perform boot operation from the
standard ROM.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)*1
QnPH
QnPRH
10000
[CONT. UNIT ERROR]
In the multiple CPU system, an error occurred in
the CPU module other than the Process CPU/High
Performance model QCPU.
Collateral information
•Common Information:–
•Individual Information:–
Diagnostic Timing
•Always
Check the details of the generated error by
connecting to the corresponding CPU module
using GX Developer.
RUN:
Off
ERR.:
Flicker
CPU Status:
Continue
Qn(H)*1
QnPH
Error
Code
(SD0)
Error Contents and Cause Corrective Action LED Status
CPU Status
Corresponding
CPU
*1 The function version is B or later.