ND-71548 (E) CHAPTER 2
Page 11
Issue 2
INSTALLATION DESIGN
5.2 Wall
Switching Equipment Room
A concrete wall is necessary so that cable racks can be installed (unless a free-access floor is used).
It is recommended that the walls be painted so that the wall materials do not generate dust, etc.
The maximum difference in level at the wall surface should be less than +5 mm (0.2 inch).
5.3 Ceiling
Switching Equipment Room
The required ceiling height is more than 2.3 meters (7.5 feet).
5.4 Lighting Facilities
1. Switching Equipment Room
Fluorescent lamps are recommended.
No less than 200 lux at the floor level is necessary.
2. Operator Room
Fluorescent lamps are recommended.
No less than 200 lux at the floor level is necessary.
3. Battery Room
Anti-explosion type lamps must be utilized.
No less than 150 lux at the floor level is necessary.
6. POWER SUPPLY REQUIREMENTS
6.1 Main Source Power
The PBX requires an operating power of -48 V DC ±5V DC. This DC operating power is supplied from the rec-
tifier which receives AC power from the commercial AC power source. For greater system reliability, it is rec-
ommended that the PBX be supplied with backup DC operating power for a predetermined duration from the
batteries installed as the auxiliary power supply source.
The batteries for the PBX must be connected in parallel with the -48 V DC output of the rectifier. Also, when
installing batteries, an EMF panel must be placed in-line (series) with the input -48 V DC supplied to the PBX.
This panel is necessary when changing the state of the rectifier from float to equalize and vice versa.