60

7-1 SR Area Flags

PC RUN Flags can be read to determine the operational status of each PC to

which a PC Link Unit is mounted. All PCs are operational when their PC RUN

Flag is ON.

If there is a transfer error or a power failure for any PC Link Unit, the Error

Flag for that Unit will turn ON, and an error message will be sent. When the

error is removed (the power comes on or transfer preparation is completed)

the Error Flag will go OFF. An error in Unit 0 stops all data transfer, but an

error in another Unit only stops that Units communication. LR bit status is

maintained whenever communication stops for one or more Units. Error

Flags will not turn ON for FALS(07) instructions; use the PC RUN Flags. The

following tables show the unit number for Single-level Systems (top line) and

the unit number followed by the level for Multilevel Systems (bottom line).

C200H, C200HS, C200HX/HG/HE(-Z), C1000H, and C2000H PCs

Bit
15 Bit 8 Bit 7 Bit 0
SR
247 #31
#15,1 #30
#14,1 #29
#13,1 #28
#12,1 #27
#11,1 #26
#10,1 #25
#9,1 #24
#8,1 #31
#15,1 #30
#14,1 #29
#13,1 #28
#12,1 #27
#11,1 #26
#10,1 #25
#9,1 #24
#8,1
SR
248 #23
#7,1 #22
#6,1 #21
#5,1 #20
#4,1 #19
#3,1 #18
#2,1 #17
#1,1 #16
#0,1 #23
#7,1 #22
#6,1 #21
#5,1 #20
#4,1 #19
#3,1 #18
#2,1 #17
#1,1 #16
#0,1
SR
249 #15
#15,0 #14
#14,0 #13
#13,0 #12
#12,0 #11
#11,0 #10
#10,0 #9
#9,0 #8
#8,0 #15
#15,0 #14
#14,0 #13
#13,0 #12
#12,0 #11
#11,0 #10
#10,0 #9
#9,0 #8
#8,0
SR
250 #7
#7,0 #6
#6,0 #5
#5,0 #4
#4,0 #3
#3,0 #2
#2,0 #1
#1,0 #0
#0,0 #7
#7,0 #6
#6,0 #5
#5,0 #4
#4,0 #3
#3,0 #2
#2,0 #1
#1,0 #0
#0,0
Error Flags PC RUN Flags
C500 PCs
Bit
15 Bit 8 Bit 7 Bit 0
SR
58 #7,1 #6,1 #5,1 #4,1 #3,1 #2,1 #1,1 #0,1 #7,1 #6,1 #5,1 #4,1 #3,1 #2,1 #1,1 #0,1
SR
62 #7
#7,0 #6
#6,0 #5
#5,0 #4
#4,0 #3
#3,0 #2
#2,0 #1
#1,0 #0
#0,0 #7
#7,0 #6
#6,0 #5
#5,0 #4
#4,0 #3
#3,0 #2
#2,0 #1
#1,0 #0
#0,0
Error Flags PC RUN Flags

AR area flags that indicate the type of System and level of the Subsystem of

the PC Link Unit mounted to the PC are also provided for C200H, C200HS,

C200HX/HG/HE(-Z), C1000H, and C2000H PCs. AR bit 2411 will be ON if a

level 1 PC Link Unit in a Multilevel System is mounted to the PC.

AR bit 2412 will be ON if a level 0 PC Link Unit in a Multilevel System or a

PC Link Unit in a Single-level System is mounted to the PC.

PC RUN and Error Flags

Level Flags

SR Area Flags Section 7-1