213
Using FINS Applications Section 8-5
Example: Network Settings (Driver Tab Page)
■ System Configuration Example 2: Using Routing Tables
In this example, an online connection is made via the Ethernet to a PLC on a
Controller Link network (PLC 3 below) from a CX-Programmer/CX-Integrator
connected to the Ethernet network.
Conditions
• FINS/UDP method
• IP address conversion: Automatic generation method (dynamic)
CX-Programmer's Change PLC Dialog Box 
Settings for target PLC (PLC3)'s Change PLC Dialog Box Setting
PLC name PLC3
Network classification Ethernet
Network Tab 
Page FINS destination FINS transmission 
source address 1
Network number 2
Node address 3
Frame length 2,000 bytes
Response monitor time 2 seconds
CX-Programmer/CX-Integrator
Ethernet port
Node address: 1 
IP address: 192.168.250.1
Ethernet or EtherNet/IP 
(network address 1)
Routing  
according to 
routing table 
Controller  
Link Unit EtherNet/IP Unit 
IP address conversion: Automatic generation method (dynamic)
Gateway between networks
PLC1
Controller Link Unit Target PLC Controller Link Unit
Node address 2 Node address 3
Controller Link 
(
network address 2
)
PLC2 PLC3
EtherNet/IP Unit node address: 2 
EtherNet/IP Unit IP address: 192.168.250.2 
EtherNet/IP Unit unit number: 0 
Controller Link Unit node address: 1 
Controller Link Unit unit number: 1
Routing to final network address 2 
requires relaying through node 
address 2 of relay network address 
1 (EtherNet/IP Unit).