CS-TE9DKE CU-TE9DKE / CS-TE12DKE CU-TE12DKE

Table (b): Outdoor Air Temperature Shifting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mode:

 

Outdoor Temperature, X (°C):

 

 

Temperature Shift (°C)

 

 

 

 

 

 

 

 

 

 

 

 

TE9DKE

 

 

TE12DKE

 

 

Cooling/Soft Dry

 

 

 

38

X

 

0.00

 

 

0.00

 

 

 

 

 

 

 

 

30

X

38

 

 

0.00

 

 

0.00

 

 

 

 

 

 

 

 

23

X

30

 

 

0.00

 

 

0.00

 

 

 

 

 

 

 

 

 

 

X

23

 

 

0.00

 

 

0.00

 

 

 

 

Heating

 

 

 

21

X

 

0.00

 

 

0.00

 

 

 

 

 

 

 

 

17

X

21

 

 

0.00

 

 

0.00

 

 

 

 

 

 

 

 

9

X

17

 

 

0.00

 

 

0.00

 

 

 

 

 

 

 

 

5

X

9

 

 

+0.50

 

 

+1.00

 

 

 

 

 

 

 

 

1

X

5

 

 

+1.00

 

 

+1.25

 

 

 

 

 

 

 

 

 

 

X

1

 

 

+1.50

 

 

+2.00

 

 

 

Table (c): Fan Speed Shifting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mode:

 

 

 

Fan Speed:

 

Temperature Shift (°C)

 

 

 

 

Cooling

 

 

 

All

 

 

+1.25

 

 

 

 

 

Soft Dry

 

 

 

All

 

 

+1.0

 

 

 

 

 

Heating

 

 

 

Lo

 

 

+1.0

 

 

 

 

 

 

 

 

 

 

 

Hi, Me-, Me, Me+, Auto

 

+0.25 (TE9DKE), +0.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(TE12DKE)

 

 

Table (d): Start-Up Shifting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mode within 60 Minutes from Start-up:

 

Temperature Shift (°C)

 

 

Cooling/Soft Dry

 

 

 

 

 

 

 

 

-1.0

 

 

 

 

 

 

Heating

 

 

 

 

 

 

 

 

+2.0

 

 

 

9.2.Indoor Power Relay Control

The Power Relay turns on under the following conditions.

1.For three minutes, when plugged in the A/C or the Error Reset button on remote controller is pressed.

2.During Installation Check Mode and following for three minutes after checking.

3.During On-timer sampling and during Preliminary operation.

4.During Operation and following for three minutes after the operation is stopped.

5.During Auto Operation, Test run, Forced Heating or Odour Removal Operation and following for three minutes after the operation is stopped.

9.3.Room Air Temperature Control (Compressor Control)

Operating frequency of a compressor is decided according to temperature differences between remote controller setting and room temperatures. A relative method which gives frequency changes, based on the decided frequency, will provide you with comfortable room environment that is not affected by operating conditions.

9.3.1.Cooling Operation

9.3.1.1.Thermostat Control

••[Intake Air Temp. - Remote Controller Setting Temp.] > [Thermostat-OFF Temp. +0.5 °C]

Operated in corresponding frequency.

••Frequency is decided after a completion of the starting control (in 60 seconds).

••When Room Temp. is below [Thermostat-OFF Temp.] continuously for 3 minutes or more, it turns to Thermostat- OFF operation.

Cooling

Power

TE9DKE

TE12DKE

Intake Air Temp.

Maximum

2.7kW

4.0kW

Difference (°C)

Rated

2.5kW

3.6kW

 

Intermediate

~

~

 

Minimum

0.8kW

0.8kW

(-1.00)

OFF

—-

—-

21