11.2. INDOOR UNIT

11.2.1.SELECT THE BEST LOCATION (Refer to “Select the best location” section)

11.2.2.HOW TO FIX INSTALLATION PLATE

The mounting wall is strong and solid enough to prevent it from the vibration.

The centre of installation plate should be at more than 450 mm at right of the wall.

The centre of installation plate should be at more than 450 mm at left of the wall.

The distance from installation plate edge to ceiling should more than 66 mm.

From installation plate left edge to unit’s left side is 20 mm. From installation plate right edge to unit’s right is 70 mm.

: For left side piping, piping connection for liquid should be this line.

:For left side piping, piping connection for gas should be about 50 mm from this line.

:For left side piping, piping connecting cable should be about 750 mm from this line.

1.Mount the installation plate on the wall with 5 screws or more.

(If mounting the unit on the concrete wall, consider using anchor bolts.)

••Always mount the installation plate horizontally by aligning the marking-off line with the thread and using a level gauge.

2.Drill the piping plate hole with ø70 mm hole-core drill.

••The centre of the right piping hole is at the intersection of lines extending vertically from the edge of the installation plate and horizontally from the sideways arrow on the installation plate. (see figure above.)

••The centre of the left piping hole is at the intersection of lines extending vertically from the downward arrow on the installation plate and horizontally from the sideways arrow on the installation plate. (see figure above.)

••Drill the piping hole at either the right or the left and the hole should be slightly slanted to the outdoor side.

CS-TE9DKE CU-TE9DKE / CS-TE12DKE CU-TE12DKE

11.2.3.TO DRILL A HOLE IN THE WALL AND INSTALL A SLEEVE OF PIPING

1.Insert the piping sleeve to the hole.

2.Fix the bushing to the sleeve.

3.Cut the sleeve until it extrudes about 15 mm from the wall.

Caution

When the wall is hollow, please be sure to use the sleeve for tube ass’y to prevent dangers caused by mice biting the connecting cable.

4.Finish by sealing the sleeve with putty or caulking compound at the final stage.

11.2.4. INDOOR UNIT INSTALLATION

1.For the right rear piping

2.For the right and right bottom piping

43