F81, F82, F83, | These codes indicate there is no voltage supplied to the primary winding of the high | ||
F84 | voltage transformer. The relationship between the codes and transformers is as | ||
| follows: |
| |
|
|
| |
|
| F81 | |
|
| F81 (NE1780J, NE1780R, NE2180) – Left transformer |
|
|
| F81 (NE2680J, NE2680R, NE3280) – Lower left transformer |
|
|
| F82 |
|
|
| F82 (NE2680J, NE2680R, NE3280) – Lower right transformer |
|
|
| F83 (NE2680J, NE2680R, NE3280) – Upper left transformer |
|
|
| F84 (NE1780J, NE1780R, NE2180) – Right transformer |
|
|
| F84 (NE2680J, NE2680R, NE3280) – Upper right transformer |
|
| NOTE: These codes are not caused by defective high voltage components |
| |
| (magnetrons, capacitor, diodes, and transformers. Replacing these |
| |
| components will not solve the problem. |
| |
| After identifying the malfunctioning circuit, perform the troubleshooting in the |
| |
| following order: |
| |
| a) | Check line fuses and replace if needed |
|
| b) | Check door for proper alignment, wear and tear, and excessive movement |
|
| c) | Check door hooks for wear and tear (it may affect the switching sequence) |
|
| d) | Check latch switch assembly and make sure that all switches operate |
|
|
| properly. Make sure they turn on and off when the door is open and closed. |
|
|
| Confirm there are free of grease and debris. NOTE: Replace all switches |
|
|
| even though only one may appear malfunctioning. |
|
| e) | Troubleshoot relays (on the low voltage board) |
|
| f) | Check controller (DPU) board for voltages necessary to actuate relays |
|
| g) | Check controller (DPU) board for cracks, poor connections, or conductive |
|
|
| residue on the component side. Clean, repair, or apply technical bulletin |
|
|
|
| |
| h) | Replace low voltage board (only if confirmed defective) |
|
| i) | Replace controller (DPU) board (only if confirmed defective) |
|
|
|
| |
F86, F87, F88, | These codes indicate malfunction one of the relays (shorted contacts). The | ||
F89 | relationship between the models and relays is as follows: | ||
| F86 – RY3 |
| |
| F87 – RY4 |
| |
| F87 – RY5 (NE2680J, NE2680R, NE3280) |
| |
| F88 – RY7 (NE2680J, NE2680R, NE3280) |
| |
| F89 – RY9 |
| |
| a) On |
| |
| NOTE: Before replacing the relays, make sure that the controller (DPU) board is free |
| |
| of residue or conductive substances (component side). Clean if necessary. |
| |
|
|
|
|
No light in the | a) | Line voltage (circuit breaker) | OCS |
cavity, no | b) | Fuses | |
display, when | c) | Cavity thermal cutout | |
the door is | d) | Thermal cutouts on all magnetrons |
|
open | e) | Voltages on controller (DPU) board – if missing, check the low voltage |
|
|
| transformer |
|
|
|
|
|