POWER GAS BURNER
clearance). Ensure plate is seated firmly against the gas spider and tighten the plate retaining screws. Recheck electrode setting as to gap and position.
15.Replace nozzle assembly; be sure to connect the flame and spark rod wires before installing nozzle assembly fully into blast tube. Check to be sure connectors on the ends of the flame and spark rod wires have a good contact. Look for properly stripped wire ends. Be sure connectors are firmly attached to the flame and ignition rod ends. Insulating boots can give a false feeling of proper seating. BE CAREFUL NOT TO MOVE ELECTRODES. Be careful not to bump electrodes Check fan wheel for free rotation.
16.Reinstall orifices in unions (if required). Reinstall burner cover.
17.Connect a test meter to the control for reading the flame response signal.
NOTE: Some controls read the flame signal in micro amps and some in volts DC. The TFM series control has two terminals marked for reading volts DC. The S89 control uses a micro amp signal for measuring flame strength. For this control, a meter must be hooked in series with the flame rod wire. Disconnect the leadwire at the S89 sensor terminal. Connect the positive lead of the meter to the
18.Be sure the tank is filled with water. Once the burner is reassembled, two devices to read pressure, preferable
19.Burners with pilot:
A.Connect the manometer to the manifold test port at the shutoff valve closest to the burner. Turn the main gas shutoff valve off. Set the air shutter as shown on the tag attached to the gas train, (see Figure
B.If nothing happens, check the control to be sure it is not in the tripped position and reset it by pushing
(3) |
flame safeguard reset button. The burner should pre- purge for not longer than thirty seconds. The TFM series control will have either an
When the blower motor starts, the air switch which proves air flow should close and terminal 6 will be powered. This starts the
Now, set the pilot pressure (measured downstream of gas valve) at the pressure shown on the tag attached to the gas train. Next, open the main gas valve slowly. Set manifold pressure at the pressure shown on the tag attached to the gas train. Do not screw the adjusting nut of the regulator in past the point where no further increase in manifold pressure is noted. Check the incoming pressure with the burner running. This is recorded as inlet flow pressure.
Our standard flow pressure requirements are:
a.5” W.C. with 8” W.C. flow on burners with inputs through 1,600,000 Btu/h.
b.8” W.C. with 11” W.C. flow on burners with inputs from 2,000,000 Btu/h through 3,200,000 But/h.
c.For inputs above 3,200,000 Btu/h, refer to the tag attached to the gas train for the correct inlet pressures.
C.If the required manifold cannot be reached, check the inlet pressure. It should be a minimum of that shown above with the burner running on full input. It is important that the incoming pressure does not fall below these minimums or nuisance control lockouts could occur.
NOTE: Where low gas pressure is a problem, special arrangements may have been made to fire the burner with reduced pressure. The appliance data decal will reflect this information.
Section 9