Type Tests

4 Type Tests

4.1 IEC 61850-3 Type Tests

Test Description Test Levels Severity
Levels
Enclosure Contact +/- 8kV 4
IEC 61000-4-2 ESD Enclosure Air +/- 15kV 4
IEC 61000-4-3 Radiated RFI Enclosure ports 20 V/m x
Signal ports +/- 4kV @ 2.5kHz x
D.C. Power ports +/- 4kV 4
A.C. Power ports +/- 4kV 4
IEC 61000-4-4 Burst (Fast
Transient)
Earth ground ports +/- 4kV 4
Signal ports +/- 4kV line-to-earth, +/- 2kV line-to-
line 4
D.C. Power ports +/- 2kV line-to-earth, +/- 1kV line-to-
line 3
IEC 61000-4-5 Surge
A.C. Power ports +/- 4kV line-to-earth, +/- 2kV line-to-
line 4
Signal ports 10V 3
D.C Power ports 10V 3
A.C. Power ports 10V 3
IEC 61000-4-6
Induced
(Conducted)
RFI
Earth ground ports 10V 3
IEC 61000-4-8 Magnetic
Field Enclosure ports 40 A/m continuous, 1000 A/m for 1 s N/A
D.C. Power ports 30% for 0.1s, 60% for 0.1s, 100% for
0.05s N/A
IEC 61000-4-29
30% for 1 period, 60% for 50 periods N/A
IEC 61000-4-11
Voltage Dips
& Interrupts A.C. Power ports 100% for 5 periods, 100% for 50
periods 2 N/A
Signal ports 2.5kV common, 1kV differential mode
@ 1MHz 3
D.C. Power ports 2.5kV common, 1kV differential mode
@ 1MHz 3
IEC 61000-4-12 Damped
Oscillatory
A.C. Power ports 2.5kV common, 1kV differential mode
@ 1MHz 3
Signal ports 30V Continuous, 300V for 1s 4
IEC 61000-4-16
Mains
Frequency
Voltage D.C. Power ports 30V Continuous, 300V for 1s 4
IEC 61000-4-17
Ripple on
D.C. Power
Supply
D.C. Power ports 10% 3
Signal ports 2kV AC (Fail-Safe Relay output) N/A
D.C. Power ports 1.5kVDC N/A
IEC 60255-5 Dielectric
Strength A.C. Power ports 2kVAC N/A
Signal ports 5kV (Fail-Safe Relay output) N/A
D.C. Power ports 5kV N/A
IEC 60255-5 H.V. Impulse
A.C. Power ports 5kV N/A
Table 17 - IEC 61850-3 Type Tests

41