Installation
Typical Motor Control Settings
|
|
|
|
| Alarm |
| Trip | Timer Trip |
|
|
|
|
|
| (Shutdown) | Setting (1) | |
Winding Temperature |
|
| 130°C |
| 155°C |
| ||
• | Class B Insulation |
|
|
|
| |||
• | Class F Insulation |
|
| 155°C |
| 170°C |
| |
Motor Bearing Temperature |
|
|
|
|
|
| ||
(Thermocouple or RTD’s) |
|
| 90°C |
| 95°C |
| ||
• | Sleeve Bearing |
|
|
|
| |||
• | Antifriction Bearing |
|
| 100°C |
| 105°C |
| |
Ground Fault |
|
| 4 Amps (2) |
| 8 Amps (2) | 0.2 sec. (2) | ||
|
| Primary |
| Primary |
| |||
|
|
|
|
| Circuit |
| Circuit |
|
Instantaneous Overcurrent |
|
|
|
|
|
| ||
• With ½ Cycle Delay |
|
| 1.8 times Locked Rotor Amps (2) |
| ||||
• | Without Time Delay |
|
| 2.4 times Locked Rotor Amps (2) |
| |||
Maximum Voltage |
|
| 110 % of Rated Voltage | 10 sec. | ||||
Minimum Voltage (the minimum voltage | 90 % of Rated Voltage | 10 sec. | ||||||
also applies to starting unless otherwise | ||||||||
specified) |
|
|
|
|
|
| ||
Maximum Frequency Deviation |
|
| ±5% | 10 sec. | ||||
Maximum of Voltage Plus Frequency Deviation |
| ±10% | 10 sec. | |||||
Maximum Voltage Unbalance (3) |
|
| 1% | 15 sec. | ||||
Maximum Current Unbalance (3) |
|
| 8% | 15 sec. | ||||
|
|
|
|
|
|
|
| |
|
|
| Suggested Vibration Limits |
|
| |||
| RPM |
| 3600 |
| 1800 |
| 1200 | 900 and |
|
|
|
|
|
|
|
| Slower |
Shaft (mils, |
| 3.3 |
| 3.7 |
| 4.3 | 5.0 | |
Housing (in./sec.) |
| 0.25 |
| 0.25 |
| 0.25 | 0.25 |
(1)Maximum time at maximum condition before control device is to operate.
(2)Increase as necessary to avoid nuisance trips.
(3)This is the maximum deviation from the average of the three phases.
- 9 -