Symmetricom 1100, 1000 manual Outstate, Rqlevel, SYS Events, Eqpt Disable Enable Disable

Models: 1100 1000

1 224
Download 224 pages 12.25 Kb
Page 172
Image 172

Chapter 6 Maintaining and Troubleshooting the TimeProvider

Troubleshooting the TimeProvider

Table 6-5. Event Codes (Continued)

Event ID

Keyword

AID

Default Value/

Description of Values

Description

TYPE

Keyword

 

 

 

 

 

 

 

FRMTYPE

Indicates the type of

T1

Output = 2M

1.544M – 1.544 MHz

 

input framing or the

 

 

2M – 2048 kHz

 

input frequency. Sets

 

 

6.312M – 6.312 MHz

 

the input framing type

 

 

CAS – CAS Input

 

 

 

 

CCS – CCS Input

 

 

 

 

ESF – Extended SuperFrame

 

 

 

 

input

 

 

 

 

CC – Composite Clock input

 

 

 

 

ISOLATED_1 – Generates an

 

 

 

 

isolated one test pattern for

 

 

 

 

T1 outputs

 

 

 

 

JCC – Japan Composite Clock

 

 

 

 

JCC4 – Japan Composite

 

 

 

 

Clock with 400 Hz

 

 

 

 

 

OUTSTATE

The specified output

T1

DISABLE

ENABLE – The output

 

state has changed

 

 

generates the defined signal

 

 

 

 

type

 

 

 

 

DISABLE – Disables the

 

 

 

 

output and clears all active

 

 

 

 

alarms associated with the

 

 

 

 

input

 

 

 

 

 

RQLEVEL

The received quality

T1

n/a

Displays the prior quality level

 

level on the specified

 

 

followed by the new quality

 

input has changed

 

 

level

 

 

 

 

 

 

 

SYS Events

 

 

 

 

 

 

CLRDELAY

Time, in seconds,

EQPT

5 s

0 to 1000 s

 

before a faulted signal

 

 

 

 

indicates it is valid as a

 

 

 

 

system reference

 

 

 

 

 

 

 

 

ELEVTIME

Indicates that Alarm

EQPT

DISABLE

ENABLE DISABLE

 

elevation time (1440

 

 

 

 

min.) is enabled or

 

 

 

 

disabled

 

 

 

 

 

 

 

 

FACTORY

Indicates that the unit

EQPT

n/a

n/a

 

has been reset to

 

 

 

 

Factory default. All

 

 

 

 

modules installed in

 

 

 

 

the system are reset

 

 

 

 

 

 

 

 

FLTDELAY

Time, in seconds,

EQPT

10 s

1 to 15 s

 

before faulted signal

 

 

 

 

indicates it is not valid

 

 

 

 

as a system reference

 

 

 

 

 

 

 

 

172 TimeProvider User’s Guide