Figure 29: Flash File Selection Window

While downloading, the RFU utility will indicate the download status. Once complete, summary information will be displayed in the bottom status bar (see Figure 30).

Figure 30: Summary Information

14.4 Wrap-Up

Once downloading is complete, close the RFU utility, move switch SW1 #1 on the ETH-100 unit back to the “OFF” (up) position to leave “firmware download” mode, and cycle power momentarily to the unit by either powering down all connected drives or momentarily removing all drive communication cables from the unit.

When the unit powers up again, it will be running the new application firmware. If the new firmware version release notes indicate that point files might need to be reloaded, then do so at this point.

When completed with MMI port use, remove the MMI cable and replace the MMI port dust cover to minimize contamination of the port’s electrical contacts.