Toshiba MMU-AP0091H 157, P13 Outdoor liquid back detection error 1. PMV1/PMV2 error, P15 / AE

Models: MMU-AP0091H

1 228
Download 228 pages 22.05 Kb
Page 157
Image 157

Check code

Check code name

Cause of operation

[P13] / [47]

Outdoor liquid back detection error 1. PMV1/PMV2 error

(TCC-L / AI-NET)

2. Pd sensor, Ps sensor error

 

3.

Clogging of SV2 circuit

 

4.

Clogging of SV3B circuit, balance pipe

 

5.

Leakage on main discharge pipe

 

6.

Outdoor I/F P.C. board error

Check code

Check code name

 

Cause of operation

 

 

 

[P15] / [AE]

Gas leak detection

1. Outdoor unit service valve closed

(TCC-L / AI-NET)

TS condition (Sub-code: 01)

2. Outdoor PMV error

 

 

3.

TS1 sensor error

 

 

4.

Refrigerant shortage, clogging refrigerant

 

 

 

circuit

 

 

5.

4-way valve error

 

 

6.

SV4 circuit error

 

 

 

 

Are connections of outdoor

NO

 

PMV1/PMV2 connectors correct?

 

 

YES

 

 

 

 

 

NO

Are operations of outdoor

 

PMV1/PMV2 normal?

 

Correct connector connection.

(CN300, CN301)

PMV error

Are service valves at gas and

NO

liquid side fully opened?

 

 

YES

 

 

 

 

 

 

Is outdoor PMV1, 2 normal?

 

1. Connector connection

NO

Open service valves fully.

YES

2. Wiring

 

3. Coil

Connectors CN300, 301 White

4. Valve body

 

Repair outdoor PMV.

Are characteristics of Pd sensor/Ps sensor

NO

 

output voltage normal?

 

YES

 

Pd sensor/Ps sensor error

5. Outdoor I/F P.C. board

YES

157

Is SV2 valve coil correctly connected?

NO

 

 

 

YES

 

 

 

 

 

YES

Is there any miswiring or

 

misinstallation on TS1 and TS2 sensors?

 

Correct connector connection.

(CV2: CN302)

Correct miswiring/installation

Are characteristics of

TS2 sensor resistance normal?

YES

Does not discharge

refrigerant gas bypass to suction side

through 4-way valve?

NO

Replace TS2 sensor. Refer to outdoor unit temperature

sensor characteristics-3.

YES

Check and replace 4-way valve and coil.

NONO

Check I/F P.C. board.

Is there no leakage of

SV41 and 42 valve circuits?

YES

Check mispiping of discharge gas/ suction gas main pipes.

Normal

Is the flow selector unit normal?

Normal

Refrigerant shortage,

clogging, pipe breakage.

NO

Repair SV41 and SV42 circuits.

( Coil, valve body, ) disconnection of cable, etc

Abnormal

Correct piping.

Abnormal

Repair the flow selector unit.

(Check there is no clogging and pipe breakage, and then recharge refrigerant.)