– 196 –
14-2. Outdoor Unit
RAV-SP1104AT-E, RAV-SP1104ATZ-E, RAV-SP1104ATZG-E
RAV-SP1404AT-E, RAV-SP1404ATZ-E, RAV-SP1404ATZG-E
Top plate
Front panel
No.
1
Part name
Common
procedure
Procedure
XCAUTIONX
Never forget to put on the gloves at working
time; otherwise an injury will be caused by
the parts, etc.
1. Detachment
1) Stop operation of the air conditioner and
then turn off switch of the breaker.
2) Remove the front panel.
(Hexagonal screw Ø4 × 10, 2 pcs.)
Remove the screws and then remove the
front panel by pulling it downward.
3) Remove the power supply cable and the
indoor/outdoor connecting wire from the
cord clamp and the ter minal.
4) Remove the top plate.
(Hexagonal screw Ø4 × 10, 5 pcs.)
2. Attachment
1) Attach the top plate.
(Hexagonal screw Ø4 × 10, 5 pcs.)
2) Connect the power supply cable and the
indoor/outdoor connecting wire to the
terminal and then fix them with the cord
clamp.
XREQUIREMENTX
For the power supply cable and the indoor/
outdoor connecting wire, be sure fix them
using the bundling band on the market along
the crossover pipe so that they do not come to
contact with the compressor, valve at gas side,
pipe at gas side and discharge pipe.
3) Attach the front panel.
(Hexagonal screw Ø4 × 10, 2 pcs.)
Remarks