CONFINED

MINIMUM AREA IN SQUARE FEET FOR UNCONFINED SPACE INSTALLATIONS

FURNACE

WITH 8 FT. CEILING

MAXIMUM BTUH

MINIMUM AREA IN SQUARE FEET

INPUT RATING

OF UNCONFINED SPACE

 

 

60,000

375

80,000

500

100,000

625

120,000

875

 

 

7

CONFINED

SPACE

1.All air from inside the building as in Figure 8: The confined space shall be provided with two perma- nent openings communicating directly with an addi- tional room(s) of sufficient volume so that the com- bined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utiliza- tion equipment installed in the combined space shall be considered in making this determination. Refer to Table 2 for minimum open areas require- ments.

2.All air from outdoors as in Figure 9: The confined space shall be provided with two permanent open- ings, one commencing within 12 inches of the top and one commencing within 12 inches of the bot- tom of the enclosure. The openings shall communi- cate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Refer to Table 2, for minimum open areas requirements.

TABLE 2

MINIMUM FREE AREA IN SQUARE INCHES

EACH OPENING (FURNACE ONLY)

Furnace

Air

Air From Outside

Maximum

From

 

 

BTUH/INPUT

 

 

Inside

Vertical

Horizontal

Rating

 

Duct

Duct

 

 

60,000

100

15

30

80,000

100

20

40

100,000

100

25

50

120,000

120

30

60

 

 

 

 

Installer’s Guide

8

9

18-CD19D6-32