Vermont Casting RADVTCEB, RADVTMB manual Install Vent Adapter Pipe, Side Wall Termination Assembly

Models: RADVTCCB RADVTVG RADVTCBS RADVTCH RADVTCBD RADVTEB RADVTCMB RADVTBS RADVTCCG RADVTCBB RAD- VTBB RADVTCSG RADVTCB RADVTMB RADVTCCH RADVTGG RADVTCEB RADVTCG RADVTBD RADVTSG RADVTCVG

1 52
Download 52 pages 13.7 Kb
Page 17
Image 17
VO584-100

1/4-20 x

Inner Adpater Pipe

 

3/8” Phil-

 

lips Screws

 

ST649

Fig. 22 Simpson DuraVent - install inner adpater pipe.

ST651

Fig. 23 Simpson Dura-Vent - install outer adapter pipe.

Install Vent Adapter Pipe

(Selkirk Corporation Vent Components)

The appliance adapter (AA) adapts DIRECT-TEMP to most direct vent appliances incorporating outlet col- lars configured to receive most common 4” (ID) by 6⁵⁄” (OD) or 5” (ID) by 8” (OD) “Twist Lock” style, direct vent systems.

The adapter incorporates two indentations on the outer wall of the inlet end, which are designed to “Twist Lock” into place upon attachment to the appliance outlet. Align the adapter indentations with the entry slots of the appli- ance outlet and slide together. Turn the adapter clock- wise approximately one-quarter turn to lock in place. The outlet end of the adapter is standard DIRECT- TEMP construction.

For connection of Direct-Temp to units with 4” x 7” flue outlets, the following methods have been approved:

Install the Universal/Napoleon Appliance Adapter 4DT-AAN.

Connect a standard Direct-Temp pipe length (do not use an adjustable length in this application) a

Radiance Direct Vent Gas Heater

minimum of 1¹⁄” over the flue outlet. The outside of the Direct-Temp Length will fit inside the flue outlet Secure with a minimum of two #8 x 1/4” sheet metal screws and seal with hi-temp silicone.

For units factory equipped with appliance adapters from other brands of Direct Vent systems, it is permissible to simply slide a length of DT pipe over the appliance adapter. Secure with a minimum of two #8 x 1/4” sheet metal screws and seal with hi-temp silicone.

Side Wall Termination Assembly

1.Locate the vent opening on the wall. Refer to Page 6, Figure 5, to determine the opening centerline.

It may be necessary to first position the stove and measure to find the hole location. Depending on whether the wall is made of combustible materials, cut the opening to the size shown in Figure 24. Com- bustible wall openings must be framed as shown in Figure 24.

CFM System

9³⁄

 

 

(240mm)

 

9³⁄

 

 

(240mm)

 

 

Combustible Wall

 

DuraVent

10”

Framing Detail

System

(254mm)

 

 

10”

 

7¹⁄₂

(254mm)

 

 

Noncombustible

NOTE: When Dura-Vent firestop is installed, Wall leave air space on top side of cut out.

Fig. 24 Locate vent opening.

2.Measure the wall thickness and cut the wall sleeve sections to proper length (MAXIMUM 12”). Assemble the sleeve with the #8 sheet metal screws supplied. Attach the firestop plate to the sleeve end with the holes. (Fig. 25) NOTE: The wall sleeve is required in combustible walls only.

3.Install the Wall Firestop/Sleeve assembly into the wall cutout and fasten the firestop to the wall cutout framing members. (Fig. 25)

For DuraVent pipe only: Install vent pipe by align- ing the locking system together, sliding the pipes together and twisting clockwise.

Install 90° elbow. Twist lock as before.

Slide the wall plate over horizontal run before at- taching the horizontal run to the elbow. Fasten wall plate to wall.

20012697

17

Page 17
Image 17
Vermont Casting RADVTCEB Install Vent Adapter Pipe, Side Wall Termination Assembly, Selkirk Corporation Vent Components