Appendix (A)

Access Control Connections

Power Connections

The control board provides a 24VDC output to power external devices and controls. Alternatively, for devices that require a power supply other than 24VDC, the operators Power Box contains a convenient 120VAC receptacle to connect a plug-in transformer.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“C”

=

Common

Terminals Connections and Input Functions:

 

 

“N.O.”

=

Normally Open

 

 

 

 

 

 

 

 

Viking Terminal

Function

 

 

Device Terminal

“+28v” ---------------------

DC Positive

---------------

 

+

“GND” ---------------------

DC Negative

---------------

 

“GND” ---------------------

Relay Common ---------------

 

“C”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“Radio”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“N.O.”

 

 

----------------------------------------

 

 

 

 

 

---------------------

 

 

 

 

 

 

 

 

 

 

If “Timer” OFF:

Open - Stop - Close

 

 

 

 

 

 

 

 

 

 

 

 

 

If “Timer” ON:

Open / Reopen if closing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(see pages 10 & 11)

 

 

 

 

 

 

 

“UL”

 

 

 

 

 

 

 

 

 

“N.O.”

 

 

 

 

 

 

 

 

If input is brief:

Stops gate then Reverses 12 inches

 

 

 

 

 

 

 

 

If input is longer:

Stops gate, does not reverse

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“Re-Open”

 

 

 

 

 

 

“N.O.”

 

 

 

 

 

 

 

 

If stopped:

No function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If closing:

Stops then Opens gate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Anti-Tailgate

 

 

 

 

 

 

 

“ATG”

 

 

 

 

 

 

 

“N.O.”

 

 

 

 

 

 

 

 

Input is received:

Stops gate if closing

 

 

 

 

 

 

 

 

 

 

 

 

 

Input is released:

Closes gate to prevent tailgating

 

 

 

 

 

 

 

 

 

 

 

 

“C. Loop”

 

 

 

 

 

 

“N.O.”

 

 

 

 

 

 

 

 

If not at open limit:

No function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If at open limit:

Prevents gate from Closing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“Open”, “Exit”, “Fire” & “Strike”

 

 

 

 

 

 

“N.O.”

 

 

 

 

 

 

 

 

If stopped:

Opens gate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If closing:

Stops then Opens gate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“Stop”

 

 

 

 

 

 

“N.O.”

 

 

 

 

 

 

 

 

If traveling:

Stops gate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“Close”

 

 

 

 

 

 

“N.O.”

 

 

 

 

 

 

 

 

If stopped:

Closes gate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If traveling:

No function

 

 

 

 

 

 