6 SPECIFICATIONS

ELECTRICAL DATA
Electrical Rating:
0 to 30 VAC 50/60 Hz. or D.C.
0.05to 1.0 Amps (Load per terminal)
1.5Amps Maximum Total Load (All terminals combined)
THERMAL DATA
Setpoint Temperature Range: 45°F to 90°F (7°C to 32°C)
Operating Ambient Temperature Range: 32°F to 105°F
Operating Humidity Range: 0 to 90% RH (non-condensing)
Shipping Temperature Range: -40°F to 150°F

7 TROUBLESHOOTING

Reset Operation

If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation you can reset the thermo-

stat by pressing and at the same time while moving the SYSTEM switch from OFF to HEAT. This also resets the factory defaults. If the thermostat has power, has been reset

and still does not function correctly contact your heating/cooling service person or place of purchase.

Batteries

For optimum performance, we recommend replacing batteries once a year with fresh “AAA” Energizer® alkaline batteries.

Symptom

Possible Cause

Corrective Action

No Heat

1.

Blown fuse or tripped circuit breaker.
Replace fuse or reset breaker.
(common problems)

2.

Furnace power switch to OFF.
Turn switch to ON.

 

3.

Furnace blower compartment door or

Replace door panel in proper position to engage safety interlock or door switch.

 

 

panel loose or not properly installed.

 

 

 

 

 

No Heat

1.

Pilot light not lit.
Re-light pilot.

 

2.

SYSTEM Switch not set to HEAT.

Set SYSTEM Switch to HEAT and raise temperature above room temperature.

 

3.

Loose connection to thermostat or system.
Verify thermostat and system wires are securely attached.

 

4.

Furnace Lock-Out Condition. Heat may also

Many furnaces have safety devices that shut down when a lock-out condition

 

 

be intermittent.

occurs. If the heat works intermittently contact the furnace manufacturer or

 

 

 

local service person for assistance.

 

5.

Heating system requires service or

Diagonistic: Set SYSTEM Switch to HEAT and raise the setpoint above room

 

 

thermostat requires replacement.

temperature. Within a few seconds the thermostat should make a soft click

 

 

 

sound. This sound usually indicates the thermostat is operating properly. If the

 

 

 

thermostat does not click, try the reset operation listed above. If the thermostat

 

 

 

does not click after being reset contact your heating and cooling service person

 

 

 

or place of purchase for a replacement. If the thermostat clicks, contact the

 

 

 

furnace manufacturer or a service person to verify the heating is operating

 

 

 

correctly.

 

 

 

 

Heat, Runs

1.

Possible short in wiring.

Check each wire connection to verify they are not shorted or touching together.

Constantly

2.

Possible short in thermostat.

No bare wire should stick out from under terminal screws. Try resetting the

 

3.

Possible short in heat system.

thermostat as described above. If the condition persists the manufacturer of your

 

 

 

system or service person can instruct you on how to test the Heat system for

 

 

 

correct operation. If the system operates correctly, replace the thermostat.

 

 

 

 

Furnace Cycles Too

1.

The location of the thermostat and/or the

Digital thermostats normally provide precise temperature control and may cycle

Fast or Too Slow

 

size of the Heating System may be

faster than some older mechanical models. A faster cycle rate means the unit

(narrow or wide

 

influencing the cycle rate.

turns on and off more frequently but runs for a shorter time so there is no

temperature swing)

 

 

increase in energy use. If you would like to increase the cycle time, clip

 

 

 

Jumper W-905 as mentioned in the instructions for Hydronic Heating Systems. It

 

 

 

is not possible to shorten the cycle time. If an acceptable cycle rate is not

 

 

 

achieved as received or by clipping W-905 contact a local service person for

 

 

 

additional suggestions.

 

 

 

 

Thermostat Setting and

1.

Thermostat thermometer setting requires

The thermometer can be adjusted +/- 3 degrees. See Temperature Display

Thermostat

 

adjustment.
Adjustment in the Operation section.
Thermometer Disagree

 

 

 

 

 

 

 

Blank Display and/or

1.

Voltage spike or static discharge.

Replace batteries and check heat/cool system for proper operation. If a voltage

Keypad Not Responding

2.

Battery change required.
spike occurs use the Reset Operation listed above.

 

 

 

 

The Emerson logo is a trademark and service mark of Emerson Electric Co.