FIG6

 

 

 

 

HOOD

 

 

POWER SUPPLY

RECEPTACLE

 

 

N G

L1

BOX

 

RECEPTACLE

 

 

 

 

PLUG

 

 

 

 

1. REMOVE SHADED TWIST ONS

 

18 B #12

 

 

2. REMOVE WIRES AT RECEPTACLE

 

18 G #11

 

 

 

 

18 W #25

1

1

 

 

18 B #24

 

 

2

2

 

 

18 BL #23

 

 

3

3

 

 

18 R #22

 

 

4

4

 

 

 

 

18 W #13

 

 

 

FOR HOODS WITH

W#20

W#10

B#1

R#4

BL#3

B#2

B7#1

B#16

B#18

B9#1

FOR HOODS WITH

 

 

 

 

 

 

 

 

 

 

HEAT LAMPS ONLY

18

18

12

18

18

18

18

18

18

18

HEAT LAMPS ONLY

CHANGE #12 & #13 TO 12GA WIRE (SUPPLIED)

 

 

 

 

 

 

 

MODEL VEN140 ONLY

 

 

 

 

 

 

 

 

POWER SUPPLY

 

 

 

 

HOOD

 

 

 

 

 

 

 

 

 

RECEPTACLE

 

 

 

 

 

N G

L1

 

 

 

 

BOX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDUIT

 

12 B #12

 

 

 

 

 

 

 

 

 

 

 

 

18 G #11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1

 

 

 

 

 

 

 

 

 

 

 

2

2

 

 

 

 

 

 

 

 

 

 

 

3

3

 

 

 

 

 

 

 

 

 

 

 

4

4

 

12 W #13

 

 

 

 

 

 

 

 

 

 

 

JUNCTION BOX

REMOTE BLOWER

GREEN

WHITE

BLACK

YELLOW

CAPACITOR

YELLOW

BLUE

RED

MOTOR

FOR HOODS WITH HEAT LAMPS ONLY

W #20

W #10

B #1

R #4

BL #3

B #2

B #17

B #16

B #18

B #19

18

18

12

18

18

18

18

18

18

18

FOR HOODS WITH HEAT LAMPS ONLY

A.Access the hood junction box, remove the designated twist on connectors, cut the four wires noted at the receptacle and remove the cut wires.

B.Access the remote blower wiring box by removing the top cover, set aside screws for later use.

C.Run four wires per local code, in conduit from remote blower to hood.

NOTE: maintain white, black, blue and red color code from blower wiring box to hood connections.

D.Connect 4-wire from blower to hood with twist-on connectors from step ￿ A; remote white to #13 (including other white wires in connection), remote black to #2 black, remote blue to #3 blue and remote red to #4 red.

NOTE: When connecting the hood to power supply, replace the black #12 wire and white #13 wire on hood with the 12 ga wires supplied with the ventilator.See Fig ￿ 6.

When remote blower is to be grounded to the Power Supply Main Ground use appropriate wire gage per local codes. See Fig ￿ 6.

If the blower is grounded through the Hood the 18 ga Green Pigtail wire at the hood Must Be Changed to 12

Ga, or Appropriate Wire Gage to Comply With Local Codes.

CAUTION: To prevent malfunction and/or harm to electrical components, connections are to be made per diagram and instructions.

E.Check rotation of blower wheel to be sure it rotates freely and does not rub brackets.

F.Replace blower top cover and screws from step ￿ B.