036-21410-001-A-0502

TABLE 12: COOLING CAPACITIES FOR DJ210 AT 115°F

RETURN AIR

 

 

OUTDOOR AMBIENT TEMPERATURE (°F): 115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

GROSS

INPUT

 

 

GROSS SENSIBLE CAPACITY1 (MBH)

 

 

CFM

CAPACITY1

POWER2

 

(RETURN AIR DRY BULB TEMP. - (°F) )

 

 

TEMP °F

 

 

 

 

(MBH)

(kW)

 

 

 

 

 

 

 

 

 

 

 

 

86

83

 

80

77

 

74

 

71

68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

197.6

19.49

125.5

108.3

 

91.2

74.1

 

57.0

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6000

67

183.1

19.04

162.2

145.1

 

128.0

110.9

 

93.8

 

76.7

59.6

 

 

 

 

 

 

 

 

 

 

 

 

 

62

176.3

18.92

176.3

160.2

 

143.1

126.0

 

108.9

 

91.8

74.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

162.8

18.55

162.8

162.8

 

145.7

128.6

 

111.5

 

94.4

77.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

204.8

19.63

137.9

119.1

 

100.3

81.6

 

62.8

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6500

67

189.9

19.18

178.3

159.5

 

140.8

122.0

 

103.3

 

84.5

65.8

 

 

 

 

 

 

 

 

 

 

 

 

 

62

182.8

19.06

182.8

174.8

 

157.4

138.6

 

119.9

 

101.1

82.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

168.8

18.69

168.8

168.8

 

160.3

141.5

 

122.8

 

104.0

85.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

212.1

19.77

150.3

129.9

 

109.5

89.0

 

68.6

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7000

67

196.6

19.32

194.4

174.0

 

153.6

133.2

 

112.7

 

92.3

71.9

 

 

 

 

 

 

 

 

 

 

 

 

 

62

189.3

19.20

189.3

189.3

 

171.7

151.3

 

130.9

 

110.5

90.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

174.8

18.82

174.8

174.8

 

174.8

154.4

 

134.0

 

113.6

93.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

213.7

19.85

165.7

142.5

 

119.2

96.0

 

72.7

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7875

67

198.1

19.40

197.0

186.8

 

167.3

144.0

 

120.8

 

97.5

74.3

 

 

 

 

 

 

 

 

 

 

 

 

 

62

190.7

19.28

190.7

190.7

 

181.9

158.6

 

135.4

 

112.1

88.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

176.1

18.90

176.1

176.1

 

176.1

152.9

 

129.6

 

106.4

83.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

215.2

19.94

181.1

155.1

 

129.0

102.9

 

76.8

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8750

67

199.5

19.48

199.5

199.5

 

181.0

154.9

 

128.8

 

102.7

76.6

 

 

 

 

 

 

 

 

 

 

 

 

 

62

192.1

19.36

192.1

192.1

 

192.1

166.0

 

139.9

 

113.8

87.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

177.4

18.98

177.4

177.4

 

177.4

151.3

 

125.2

 

99.1

73.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro- priate blower performance table for the kW of the supply air blower motor.

2.These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.

Unitary Products Group

21

Page 21
Image 21
York 300 warranty Cooling Capacities for DJ210 AT 115F