York YVC, YWC, YVF/YVS warranty Installation

Models: YVF/YVS YWC YVC

1 12
Download 12 pages 43.37 Kb
Page 3
Image 3
INSTALLATION

FORM 115.20-NOM3 (1006)

INSTALLATION

RECEIVING

Material in this shipment has been inspected at the factory and released to the transportation agency in good condition. When received, a visual inspection of all cartons should be made immediately. Any evidence of rough handling or apparent damage should be noted on the delivery receipt and the material inspected in the presence of the carrier's representative.

If damage is found, a claim should be filed against the carrier immediately.

STORAGE

If the equipment is not to be immediately installed, store it in a dry location with the motor protected against moisture, dust, corrosion and physical damage.

PREPARE WALL FOR MOUNTING

Depending upon building construction, provisions for mounting the unit must be made by the contractor according to architects; drawings.

1.Pull firmly on the lower cabinet door (each side) until the cabinet releases from its friction fastener.

2.Proceed to lift the door assembly straight up and off the cabinet frame.

YVC UNIT STYLE ( VERTICAL CONCEALED)

See Fig 8 for unit details and dimensions.

Mounting location must allow enough clearance to permit the removal of screws that secure the cabinet panels. After selecting the location for the unit:

1.Remove the front panel.

2.Position the unit in its permanent location, making sure it is level to insure proper drainage and opera- tion, and secure the unit in place.

3.Secure the unit to the wall using the four, 1/2 inch holes provided (two on each end of the unit).

Access must be provided for servicing the unit. If this access is provided by a removable panel, ample space must be allowed for access to electrical and plumbing controls.

YWC UNIT STYLE (RECESSED WALL)

See Fig 9 for unit details and dimensions.

It is recommended that all mounting holes be used for proper installation.

Unit must not be operated during building construction due to excessive airborne dust and debris. The units must not be operated under any cir- cumstances without an air filter in place.

YVS / YVF UNIT STYLE (VERTICAL CABINET)

See Fig 7 for unit details and dimensions.

Mounting location must allow enough clearance to permit the removal of screws that secure the cabinet panels. After selecting the location for the unit, remove the front panel. The front panel must be removed on the YVS or YVF unit to gain access to the coil, drain connections and electrical junction box. To accomplish this:

Mounting location must allow enough clearance to permit the removal of all mechanical parts within the unit.

1.Frame the unit as required so the front panel of the wall unit will be flush with the drywall surface when installed.

2.Frame around the perimeter of the unit as required for securing the drywall. See Table 1 below for drywall openings.

MODEL NUMBER

DRYWALL CUTOUT DIM

 

HT x WD

3YWC

28 x 42

4YWC

28 x 50

6YWC

28 x 58

8YWC

28 x 66

10YWC

28 x 74

12YWC

28 x 82

TABLE 1 – DRYWALL OPENINGS

YORK INTERNATIONAL

3

Page 3
Image 3
York YVC, YWC, YVF/YVS warranty Installation