2. Installation

2.4 PROFIBUS DP Network Construction

Network Configuration

A PROFIBUS DP network is configured as shown in the following figure.

 

Master 1

Network

Master 2

 

 

Terminating

Cable

 

 

 

 

 

 

 

 

Resistor ON

 

 

 

 

 

Terminating

 

 

 

 

 

 

 

 

Slave

Slave

Slave

Slave

Slave

 

Resistor ON

Terminating

 

 

 

 

 

Repeater

 

 

 

 

 

 

Resistor ON

 

 

 

 

 

Terminating

 

Slave

Slave

Slave

Slave

Slave

 

Resistor ON

 

 

 

Station

There are four types of stations (devices): master, slave, repeater, and configurator. The master controls a network and gathers its slaves.

The slave, including external I/O and other devices, outputs data as a response to a master’s output order and informs the master of its input status.

The repeater is necessary for a network with more than 32 slaves to separate network segments.

The configurator, used only for network installation, configures a scan list of the slaves on the master device.

You can install masters anywhere on the network. You can connect up to 126 stations including server and repeater on your network. However, we recommend you to use one device for the engineering device.

Network Cable

The PROFIBUS cable can be used as a network cable. There are four types (A, B, C, D) of PROFIBUS cables. Normally, cable type A is used for a PROFIBUS DP network. The cable type A specifications are shown in the table below.

Item

Specification

Impedance

135 to 165

Capacity

< 30 pf/m

Loop resistance

110 Ω/km

Wire diameter

0.64 mm

Core cross-section

> 0.34 mm2

20

Fieldbus I/O Rev.6

Page 32
Image 32
Epson EM07ZS1647F manual Profibus DP Network Construction, Station, Network Cable