Necessary sensor by operating mode

Necessary sensor by operating mode

Operating mode

Necessary sensor

Function

 

 

 

 

 

- This runs indoor air conditioning.

Air conditioning

SA temperature sensor

- Initial external air inlet setting is 30% of the air

supply during the air conditioning and this can be

RA temperature sensor

 

changed by the user. But, when the damper actuator

 

 

 

 

is installed on AHU, the setting can be changed.

 

 

 

 

 

- This runs the indoor heating.

Heating

SA temperature sensor

- Initial external air inlet setting is 30% of the air

RA temperature sensor

supply during the heating and this can be changed

 

 

by the user. But, when the damper actuator is

 

 

 

 

installed on AHU, the setting can be changed.

 

 

 

 

 

- This is the operating function to run indoor air

 

 

conditioning by controlling multiple outdoor units by

 

SA temperature sensor

comparing the enthalpy of the indoor/outdoor air.

 

- During the power save operation, the operation switches

Power save

RA temperature sensor

between partial air conditioning operation (Controlling

OA temperature/

multiple outdoor units) and external air conditioning

 

humidity sensor

operation (Outdoor unit OFF, 100% external air flow).

 

Damper actuator

- This is operating function is mainly used in between

 

seasons. But if there is no OA temperature/humidity

 

 

 

 

sensor and RA temperature/humidity sensor on the

 

 

AHU, the power save operation cannot be selected.

 

 

- This is the operating function to remove the indoor

 

SA temperature sensor

humidity when the humidity level indoor is excessive.

Dehumidify

RA temperature sensor

- During the dehumidifier operation, the set value is

50%RH and the user cannot change this setting. But

OA temperature/

 

if there is no OA temperature/humidity sensor and

 

humidity sensor

 

RA temperature/humidity sensor on the AHU, the

 

 

 

 

dehumidifier operation cannot be selected.

 

 

 

 

 

- This is the operating function to control the humidity to

 

SA temperature sensor

the set value by detecting the indoor humidity level.

Humidification

- This can be selected during heating operation.

RA temperature sensor

But if there is no humidifier/humidifying valve and

 

 

 

RA temperature/humidity sensor on the AHU, the

 

 

humidifier operation cannot be selected.

 

 

 

 

 

- This is the operating function to control the amount of

 

 

external air flow so that the CO2 level is controlled

 

SA temperature sensor

within the set level by detecting the indoor CO2 level.

 

- The initial CO2 level is set to 1000ppm, and can

Auto ventilation

RA temperature sensor

be changed by the user.

CO2 sensor

- This function operates when auto ventilator

 

 

Damper actuator

(Additional operation) is selected during air

 

 

conditioning or heating operation. But if there is no

 

 

CO2 sensor and damper actuator on the AHU, the

 

 

auto ventilator operation cannot be selected.

 

 

 

 

SA temperature sensor

- When the mixing temperature during the heating

 

operation is below the set value (5°C),

Preheating

RA temperature sensor

preheating device automatically operates. The

Mixing temperature/

preheating device and mixing temperature

 

 

humidity sensor

sensor must be installed on AHU for this to

 

 

operate automatically.

 

 

 

 

 

 

6AHU CONTROL KIT

Page 6
Image 6