3-PHASE FX SYSTEM

This system produces 120VAC per phase and 208VAC from phase to phase. There can only be one FX per phase on a 3-phase system.

The non-Mobile AC wiring from the AC source and to the AC loads must handle 60 amps AC.

All other non-Mobile AC wiring must handle a capacity of 60 amps AC; Mobile must handle 30 amps AC.

This system can power continuously up to 10.8kW of loads depending on which model is used.

Connecting more power than the continuous rating of the FX may cause breakers to trip or the FX to shut off its AC output.

The jumper in the HUB must be moved for 3-phase configuration (please see the HUB Installation and User Guide).

Note: Program the bottom FX as Master (3ph MASTER) and the two lower FXs as 3-phase Slaves

(3ph SLAVE). Keep the phases in order: phase one is connected to the FX programmed L1; phase two is connected to L2; and phase three to L3 (or phases A, B, and C to inverters A, B, and C).