2. Expanded Functions

T3H (self-station)

RW100

RW101

RW227

TOSLINE-S20LP

Station No. 3

T3H (target-station)

D1000

D1001

D1127

When R0020 is ON, 128 words data starting with RW100 is transferred to D1000 and after of the T3H on which station No. 3 S20LP is installed.

When the operation is completed, the status is set in RW050 and instruction output comes ON.

Note

Keep the input ON until the output comes ON.

This instruction becomes error complete in the following cases. (ERF = S0051 is set to ON)

(1)Target station No. is invalid. (for S20LP)

(2) Invalid register designation. (In case of T and C registers, T T and C C is only possible)

(3)Source/destination register address range is out of valid range.

(4)Destination register is write-protected.

(5)Response time-out is occurred.

(6)If expanded F register is designated;

-when MMR setting is not made.

-when IC card is not installed.

-when IC card is used to store program.

-when IC card is write-protected. (for destination)

By using SW067, register write-protect is available against SEND instruction of other T3H.

SW067

F

9

8

7

6

5

4

3

2

1

0

 

SW

C

T

 

F

D

RW

LW

W

YW

0: Write enable

Both F register in CPU and

1: Write protect

expanded F register in IC card

 

Resetting the status register (operand B) is necessary at the first scan.

When using the TOSLINE-S20LP or Ethernet module (EN311), read the manual for these network modules.

User’s Manual 65