Redring 600, 620 manual Diagram

Page 9

Cable Sizes

Fuse/ MCB

7.5

/ 6.9kW 240/230V 6mm²

40A Cartridge fuse Type A MCB 14m max

8.5

/ 7.8 kW 240/230 V 6mm²

40A Cartridge fuse 14m max Type A MCB 22m max

9.5

/ 8.7kW 240/230V 10mm²

40 or 45A Cartridge fuse 22m max

You may be able to use 6mm² cable if Method 1 (clipped direct) is used.

Remember to up-rate the cable if it runs in thermal insulation in a loft, or for a longer distance.

3.A means for disconnection in all poles must be incorporated in the fixed wiring in accordance with the wiring rules. We recommend ceiling switches.

4.Cut back cable as in diagram 10. Connect cable to terminal block making sure that ALL the retaining screws are VERY tight and that no cable insulation is trapped in the block.

Diagram 11

WARNING - FAILURE TO COMPLY WITH THESE

INSTRUCTIONS COULD RESULT IN A FAILURE

OF THE TERMINAL BLOCK AND CABLING.

5.WARNING - THIS APPLIANCE MUST BE EARTHED.

6.Ensure that the removable side section is fitted securely back into the back-plate.

7.Fit the front cover into position making sure the knob is aligned correctly with the flow valve (see diagram 12).

WARNING - TAKE CARE WHEN REPLACING THE FRONT COVER TO AVOID DAMAGING ANY COMPONENTS.

8.Operate the shower first without the handset to flush out any particles, fit handset and then operate the shower as explained previously and check:

a)That the water gets to a satisfactory temperature.

b)Power selection does give a change in water temperature.

c)Check again for leaks.

9

Image 9
Contents Please retain this booklet for future reference Contents How to use your showerHow your shower works Redring After Sales ServiceDiagram What to do if things go wrong Installation instructions Diagram Plumbing see diagram Electrical Connections Handset or the Pressure Relief DeviceDiagram How to maintain your shower Additional Accessories Catalogue NumberSpares Diagram Morley WAY, PETERBOROUGH. PE2 9JJ