Specification for SiteLink-4
DESCRIPTION: The SiteLink-4 is a 32 bit microprocessor-based communications device that provides an interface for up to four Liebert Unit Controllers (IGM’s). The SiteLink-4 communicates to either the SiteScan Monitoring System, or a third party software program utilizing a designated open standard protocol (i.e. Modbus or BACnet). This device communicates to the SiteScan Monitoring System via a twisted pair called the ARC156 network through an EIA-485 port at either 156K / 9600 or 38.4kbps baud. It communicates to the third party software monitoring system via a 9-pin DTE male EIA-232 connector (Portal Interface) or at the 5 pin EIA485 port communicating at either 9600bps or 38.4kbps baud. Four EIA-422 ports are provided to connect Liebert Information Gathering Modules.
DIMENSIONS: | Module: | 7 1/2" H x 11 1/4" W |
| | 19.05cm H x 28.58cm W |
| Enclosure: | 12”H x 14.25" W x 2.85" D |
| (painted steel) | 419.1mm x 301.3mm x 78.6mm |
See Enclosure Diagrams for mounting options.
POWER:24VAC ± 10%, 50-60 Hz., 7.2VA power consumption (120/24VAC 40VA transformer available).
ENVIRONMENTAL
OPERATING RANGE: 0° to 130° F (-17.8°to 54.4° C), 10 to 90% relative humidity, non-condensing
COMMUNICATION: CMnet EIA-485 Port - Control Module network screw terminals Switch selectable baud rates ARC156 / 9600 or 38.4bps Recommended wire is: MAGNUM Cable pn A3-ARC-156-2
Two (2) Portal Interface – One EIA-232, One EIA-485 2 / 4 wire (for Third Party software selectable baud rate, 9600bps or 38.4kbps
One (1) Access port (for diagnostics)
Four (4) EIA-422 Ports (for Liebert unit connection) - screw terminal
MEMORY:1024 kB Flash memory and 1024 kB non-volatile battery-backed RAM.
PROTECTION: Voltage, current, and ESD protection on incoming power and CMnet.
Liebert Corporation | Page 1 of 5 | SL-27213 Rev. 4; 7/03 |