Emerson 5500 SERIES, A5510 installation manual Thin Web Server Troubleshooting

Page 34

Thin Web Server

Troubleshooting

Troubleshooting

Symptom

1.Thin Web server (TWS) does not turn ON.

2.Thin Web Server keeps rebooting.

NOTE: You should hear a series of beep sounds to indicate the TWS is scanning. When it completes the process you will hear a ring sound similar to a cell phone ring.

3.Corrupted 72E IP address list after downloading 72E list at TSSP.

4.No response from TWS after power is applied. Normally you should hear a beep sound to indicate that the system is scanning for ASCO device.

Possible Problem

.

Corrupted usercfg.bin

Corrupted _72Ebin file.

TWS is not rebooting..

Possible

Action

Prevention

Cause

 

 

.

– Check if you have the correct power supply.

 

 

– Make sure the plug is connected properly to the supply

 

 

outlet.

 

– Interrupted

a. Connect a PS2 keyboard to the TWS.

– Make sure that the version of

configuration

b. At the next reboot, press the u key intermittently.

the TSSP and TWS firmware

upload.

c. When you hear a ring sound, this will indicate that the

are the same.

– TSSP and TWS

usercfg.bin file of the TWS has been erased.

– Unload old version of the

versions

d. You should then reset the TWS mnually from here.

TSSP you’re your computer

mismatch.

e. Once it reboots, rerun your TSSP, check all your settings

first, then install the new

 

and download again.

version before using it with

 

f. Reset the TWS after download.

the TWS.

 

g. Repeat steps b – f if necessary until symptom is resolved.

– Make sure to allow the

 

NOTE: If sympton persists after repeating this procedure

system to complete the

 

several times, the TWS may be damaged. Contact ASI for

down-load process before

 

service.

doing any tasks.

Interrupted

a. Connect a PS2 keyboard to the TWS.

Make sure to allow the system

configuration

b. At the next reboot, press the e key intermittently.

to complete the down-load

upload.

c. When you hear a ring sound, this will indicate that the

process before doing any tasks.

 

_72Ebin. file of the TWS has been erased.

 

 

d. You should then reset the TWS mnually from here.

 

 

e. Once it reboots, rerun your TSSP, check all _72E record

 

 

settings and download again to the TWS.

 

 

f. Reset the TWS after download.

 

 

g. Repeat steps b – f if necessary until symptom is resolved.

 

 

NOTE: If sympton persists after repeating this procedure

 

 

several times, the TWS may be damaged. Contact ASI for

 

 

service.

 

– Hard disk

– Power fluctuation.

Call ASI for assistance.

damaged in

– Incorrect supply applied to TWS.

 

TWS from

 

 

mishandling.

 

 

Disk file corruption from incomplete file transfer / upward.

Image 34
Contents Client Settings Setup ProcedureConnectivity Module Configuration GeneralThin Web Server Who Should Use this Installation Manual WelcomeThin Web ServerOverview, Specifications, Ground Connection Thin Web Server OverviewMount the Thin Web Server Thin Web Server MountingPage Connect the ATS Network Connect the PowerThin Web Server Connections Page Page Page Page Page Page Page Page How to Install the Setup Program for Serial Connection  Minimum PC Requirements for Setup and Browser ProgramsThin Web Server Setup Program Serial Connection Setup Program Serial Connection Thin Web Server How to start and setup the Thin Web Server software Alarms Engine Power Manager Setting Ö Un-installing the program Http//169.254.1.2/config.htm Thin Web Server Setup Ethernet ConnectionThin Web Server File Management Utilities How to copy, delete, and view files in the Thin Web ServerTo update firmware, to update documentation Serial ConnectionEthernet Connection Thin Web Server SSL Certificate & Private Key Files Connectivity Module Configurator Program Thin Web Server Connectivity Module ConfigurationHow to Delete Configuration Setting Connectivity Module Configuration Thin Web ServerHow to Edit Configuration Setting How to Upload Configuration SettingHow to Test Email Feature How to Reset Thin Web Server SeriallyOther Utilities How to View TWS MAC Address Thin Web Server How to View the TWS MAC AddressThin Web Server Client Settings Client Settings Thin Web Server \ pingThin Web Server Client Settings Client Settings Thin Web Server Troubleshooting Thin Web Server TroubleshootingTWS LAN Tssp Go to Utilities , Server File Management and delete Communication Address Form Communication Address Form Communication Address Form Communication Address Form Index

5500 SERIES, A5510 specifications

The Emerson 5500 Series, specifically the A5510 model, is a cutting-edge solution in the field of measurement and control, renowned for its reliability and precision in industrial applications. This versatile device is primarily used in various sectors, including oil and gas, water treatment, and manufacturing processes, where accurate monitoring and control of parameters such as pressure, temperature, and flow are critical.

One of the main features of the Emerson A5510 is its advanced digital communication capabilities. It supports various industrial protocols such as HART, Modbus, and Profibus, allowing for seamless integration with existing control systems. This connectivity ensures real-time data exchange, enabling operators to make informed decisions quickly and effectively.

The A5510 is equipped with robust diagnostic tools that enhance operational efficiency. Users benefit from features like predictive maintenance alerts and comprehensive data logging, which facilitate troubleshooting and help prevent unexpected failures. This proactive approach to maintenance not only reduces downtime but also extends the device's lifespan.

The device boasts a highly intuitive user interface, which simplifies the configuration and calibration process. Operators can easily navigate through its menu to customize settings according to specific application requirements. This user-centric design minimizes training time and helps users maximize the device's capabilities.

In terms of construction, the Emerson A5510 is designed for durability in harsh environments. It is built with high-grade materials that provide excellent resistance to corrosion and extreme temperatures. This robustness ensures that the device remains operational even in challenging industrial settings, maintaining accuracy and reliability.

The A5510 also features advanced signal processing technology that enhances measurement fidelity. It effectively filters out noise and minimizes the impact of environmental variables, ensuring that the readings are both stable and accurate. This is particularly beneficial in applications where precision is paramount.

Additionally, Emerson emphasizes sustainability and energy efficiency in the design of the 5500 Series. The A5510 is engineered to consume minimal power while delivering top-notch performance, aligning with the industry's growing focus on reducing energy consumption and environmental impact.

In summary, the Emerson 5500 Series A5510 is a sophisticated measurement and control device that combines advanced technology, durability, and user-friendly features. Its digital communication capabilities, robust diagnostics, and energy-efficient design make it an ideal choice for businesses seeking to optimize their operations and enhance their monitoring processes. With the A5510, Emerson continues to set the standard for innovation and reliability in industrial measurement solutions.