Emerson GDESIGN 10003000 A, 386 manual Sensor Adjustments, How to Change a Setting

Page 10

SECTION 4 ADJUSTMENTS

Sensor Adjustments

Voltage and frequency sensor pickup and dropout points are factory set as specified on the Wiring Diagram. The frequency setting can be set for 50 or 60 Hz.. To change this setting, follow the procedure below. Use Table 4-1 for the setting and corresponding DIP switch actuator.

NOTICE

Do not change any other factory settings. Any change in these settings may affect the normal operation of the ASCO 386. This change could allow the load circuits to remain connected to a low voltage source.

Table 4-1. Frequency Settings. ( Shaded DIP switch is standard factory setting).

DESCRIPTION

LABEL

FACTORY

ADJUSTMENT

S1 DIP SWITCH

SETTING

RANGE

 

 

 

 

 

 

Frequency

60 / 50 Hz

60 Hz

60 Hz

Actuator 4 off

 

 

 

 

 

50 Hz

Actuator 4 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 4

 

thumb

cover

latch

 

hook on left side

Figure 4-1. Controller cover latch.

How to Change a Setting

NOTICE

Do not make any setting changes while the controller is energized.

1.Deenergize all power, then open the enclosure door.

2.Disconnect both harness plugs from controller by squeezing the latches. Do not pull on the wires.

3.Remove cover from the controller by releasing latch on right side with your thumb. See Figure 4-1.

4.Locate the appropriate adjustment DIP switch for the setting that you want to change. Refer to Table 4-1 above and Figure 4-2 and Figure 4-3.

5.Use a ball-point pen (or similar pointed tool) to slide the switch actuators left or right so they match the illustration next to the setting (left = off, right = on). Recheck the setting. See Figure 4-3.

6.Install the cover on the controller by hooking it on the left side and latching the right side.

7.Reconnect both harness plugs to the controller by aligning and pressing straight in until latches click.

8.Close the enclosure door, then restore both sources.

harness plugs

S1 DIP switch

S2 DIP

(load disconnect feature)

switch

see page 5--- 1

Figure 4-2. Location of DIP switch.

DIP switch S1

actuator

(8 on each DIP switch)

off on

Figure 4-3. Setting DIP switch actuator.

4---1

Image 10
Contents Rating Label Table of ContentsIdentification Label Page Installation Line Connections Testing Power ConductorsConnecting Power Conductors Bus ConnectionsManual Operation Test ClosedVoltage Checks Electrical OperationTransfer To Emergency Section Sequence of OperationRetransfer to Normal Testing Section Testing & ServicePreventive Maintenance Replacement PartsTROUBLE-SHOOTING Manual Load TransferSensor Adjustments AdjustmentsHow to Change a Setting Delay Before Transfer Optional FeaturesDelay After Transfer Index