Owner’s | ATS Annunciator |
Manual | Catalog 214A400, 214A401, 214A404 |
DANGER is used in this manual to warn of high voltages capable of causing shock, burns, or death.
!
WARNING is used in this manual to warn
of possible personal injury.
!
CAUTION is used in this manual to warn
of possible equipment damage.
Master ATS Annunciator
Catalog 214A400, 214A404
General
There are three types of ATS (Automatic Transfer Switch) Annunciators. They are identified as follows:
Catalog 214A400 Master Unit
Catalog 214A404 Master Unit used with a Network Supervisor
Catalog 214A401 Slave Unit
Each installation must have a master unit; each master unit can support two slave units. Each unit can annunciate four ATSs. Therefore a master and two slave units can annunciate up to twelve ATSs. To annunciate more ATSs, additional masters and slaves can be added.
ASCO Catalog 214A400, 214A404, and 214A401 ATS Annunciators are designed to provide remote visual status reporting and push button testing of ASCO automatic transfer switches. Each ATS must have a Group 1*, 5, 6, or 7 Microprocessor Controller with Accessory 72A Serial Communication Interface Option installed.
*Note: Group 1 Controller must have version 8 or lower software (dash number on microprocessor).
| Ratings |
Nominal Input Voltage | . . . . . . . . 16 V ac 50 or 60 Hz, |
| . . . . . . . . . . . . or 12 or 24 V dc |
. . . . . . . 10 VA max @ 16 V ac | |
| . . . . . . . 0.5 A max @ 24 V dc |
Environmental Temperature Range
Transient Withstand | per NEMA ICS | |
Surge Withstand (SWC) | . IEEE Std 472 | |
. . . . . . | ANSI C37.90A |
Max total distance for Communication Line 4000 ft ➁
➀(Master with 2 Slaves)
➁For greater distances contact ASCO.
Catalog 214A401
Slave ATS Annunciator
An experienced licensed electrician must install the ATS Annunciator.
Table of Contents | |
| |
Iinstallation | . . . . . . . . . |
Setting Up the ATS Annunciator . . | . . . . . . . . . |
Operation and ATS Testing | . . . . . . . . . . 6 |
Troubleshooting | . . . . . . . . . . 7 |
50 Hanover Road, Florham Park, New Jersey | |
For sales or service call 1 800 |
|
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3 telephone 519