Emerson 214A404, 214A401, 214A400 owner manual General, Ratings, Table of Contents

Page 1

Owner’s

ATS Annunciator

Manual

Catalog 214A400, 214A401, 214A404

DANGER is used in this manual to warn of high voltages capable of causing shock, burns, or death.

!

WARNING is used in this manual to warn

of possible personal injury.

!

CAUTION is used in this manual to warn

of possible equipment damage.

Master ATS Annunciator

Catalog 214A400, 214A404

General

There are three types of ATS (Automatic Transfer Switch) Annunciators. They are identified as follows:

Catalog 214A400 Master Unit

Catalog 214A404 Master Unit used with a Network Supervisor

Catalog 214A401 Slave Unit

Each installation must have a master unit; each master unit can support two slave units. Each unit can annunciate four ATSs. Therefore a master and two slave units can annunciate up to twelve ATSs. To annunciate more ATSs, additional masters and slaves can be added.

ASCO Catalog 214A400, 214A404, and 214A401 ATS Annunciators are designed to provide remote visual status reporting and push button testing of ASCO automatic transfer switches. Each ATS must have a Group 1*, 5, 6, or 7 Microprocessor Controller with Accessory 72A Serial Communication Interface Option installed.

*Note: Group 1 Controller must have version 8 or lower software (dash number on microprocessor).

 

Ratings

Nominal Input Voltage

. . . . . . . . 16 V ac 50 or 60 Hz,

 

. . . . . . . . . . . . or 12 or 24 V dc

Volt-Ampere Burden

. . . . . . . 10 VA max @ 16 V ac

 

. . . . . . . 0.5 A max @ 24 V dc

Environmental Temperature Range ---20˚C. to +70˚C.

Transient Withstand

per NEMA ICS 1---109

Surge Withstand (SWC)

. IEEE Std 472

---1974

. . . . . .

ANSI C37.90A

---1974

Max total distance for Communication Line 4000 ft

(Master with 2 Slaves)

For greater distances contact ASCO.

Catalog 214A401

Slave ATS Annunciator

An experienced licensed electrician must install the ATS Annunciator.

Table of Contents

 

section-page

Iinstallation

. . . . . . . . . 1-2

Setting Up the ATS Annunciator . .

. . . . . . . . . 3-5

Operation and ATS Testing

. . . . . . . . . . 6

Troubleshooting

. . . . . . . . . . 7

50 Hanover Road, Florham Park, New Jersey 07932–1591 USA

381333–063 B

For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com

 

ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3 telephone 519 758–8450, fax 519 758–0876, for service call 1 888 234–2726 (ASCO) www.asco.ca

Image 1
Contents General Table of ContentsRatings Connecting Slave ATS Annunciators InstallationMounting Communication Wiring Power WiringNetworks for Interconnecting ATS Annunciators and ATSs Setting the ATS Address Number Setting UP the ATS AnnunciatorsSet Number of Masters and Master Address Set Number of SlavesSetting UP the ATS Annunciators Setting UP the ATS Annunciators ATS Annunciator Master OperationProblem Probable Cause Corrective Action TROUBLE-SHOOTING