Emerson 300 manual Testing & Service, Manual Load Transfer, Trouble-Shooting

Page 12

TESTING & SERVICE (continued)

MANUAL LOAD TRANSFER

This procedure will manually transfer the load if the controller is disconnected.

Do not manually operate the transfer switch until both power sources are disconnected: open both circuit breakers.

1.Open normal and emergency source circuit breakers.

2.Use the maintenance handle to manually operate transfer switch to the opposite source. See page 1–3, Manual Operation Test.

3.If the transfer switch is in the Emergency position manually start the engine generator and then close the emergency source circuit breaker.

TROUBLE-SHOOTING

Note the control features that are activated or furnished on the switch and review their operation. Refer to Section 5, Control Features.

Proceed with care! The automatic transfer switch is energized.

Table 3-1. Trouble-Shooting Checks.

PROBLEM

CHECK IN NUMERICAL SEQUENCE

1 OPERATION

2 GEN-SET

3 VOLTAGE

 

Gen-Set does not start when

Hold the Transfer Test button

Starting control must be in

 

the Transfer Test button is

15 sec. or the outage must be

automatic position. Batteries

 

pressed and held for 15

long enough to allow for the 1

must be charged and

 

seconds or when the normal

or 3 sec. Momentary Normal

connected. Check wiring to

source fails.

Source Outage Delay plus

engine starting contacts.

 

 

engine cranking and starting

 

 

 

time.

 

 

 

 

 

 

Transfer switch does not

Wait for Transfer to Emergen-

Generator output circuit

Voltmeter should read at least

transfer the load to

cy Delay (0 to 5 min.) to time

breaker must be closed.

90% of nominal phase to

emergency source after the

out. For immediate transfer,

Generator frequency must be

phase voltage between

gen-set starts.

press the Bypass Time Delay

at least 57 Hz.

transfer switch terminals EA

 

button. If Motor Load Transfer

 

and EC (or EL1 and EL2 for 2

 

is active, wait for inphase con-

 

pole switches). *

 

dition (see below).

 

* These are factory settings.

 

 

 

 

Transfer switch does not

Wait for Retransfer to Normal

 

Voltmeter should read at least

transfer the load to normal

Delay (1 sec. to 30 min.) to

 

90% of nominal phase to

source when normal returns

time out. For immediate re–

 

phase voltage between

or when Transfer Test button

transfer, press Bypass Time

transfer switch terminals NB

is released.

Delay button. If Motor Load

 

and NC, NC and NA, and NA

 

Transfer is active, wait for in-

 

and NB (or NL1 and NL2 for 2

 

phase condition (see below).

 

pole switches).

 

 

 

 

Gen-Set does not stop after

Wait for the 5 minute

Starting control must be in

 

load retransfer to the normal

Unloaded Running Delay to

automatic position.

source.

time out.

 

 

 

 

 

 

Trouble-Shooting the Motor Load Transfer Feature (refer to page 5–4)

Use extreme caution when using a meter to measure voltages in the following steps. Do not touch power terminals; shock, burns, or death could result !

1.Connect a voltmeter (set for twice system phase–to–phase voltage) between Transfer Switch terminals NA and EA.

2.Manually start generator. Voltmeter needle should sweep back and forth at a regular rate between 0 and about twice system voltage.

3.Press and hold Transfer Test button. The load should transfer to emergency source when meter needle is near 0 volts. If transfer does not occur, Motor Load Transfer feature is not operating.

4.Release the Transfer Test button. The load should retransfer back to the normal source after the Retransfer to Normal Delay, if used. The retransfer should occur when the needle is near 0 volts. If retransfer does not occur after the time delay, the Motor Load Transfer feature is not operating.

5.For immediate retransfer, press the Bypass Time Delay button. Then disconnect the voltmeter.

If the problem is isolated to circuits on the controller or the transfer switch, call your local ASCO Power Technologies sales office, representative, or ASI. In the United States, call 1–800–800–2726. Furnish the Serial No., Bill of Material (BOM) No., and Catalog No. from transfer switch nameplate.

3---2

Image 12
Contents Operator’s Manual Rating LabelPage Nameplate Catalog Number Identification EnclosurePage Installation SectionLeft side Transfer switch Table A. Engine start Connections Engine Starting ContactsAuxiliary Circuits Connections to ControllerInstallation Functional Test Manual Operation TestInstallation Voltage ChecksElectrical Operation Sequence of Operation Transfer To EmergencyRetransfer to Normal Testing & Service Preventive MaintenanceDisconnecting the Controller Testing & Service TROUBLE-SHOOTINGManual Load Transfer Adjustments Time Delay AdjustmentSensor Adjustments Time Delay SettingsAdjustments How to Change a SettingSwitches SW3 actuator On each DIP switch Off onControl Features Engine Exercisers DIP Switch SettingsHow to Set Built-In Timer BUILT-IN Engine ExerciserControl Features Programmable Engine Exerciser ModuleDaylight Savings Time Adjust Display Fast / Slow Adjust DisplayFill in your settings for future reference Run Time DisplayRemote Control Features Inphase Monitor For Motor Load TransferLoad Disconnect Feature Control Features Optional Strip Heater Accessory Strip Heater AccessoryAvailable Kits ControlsIndex
Related manuals
Manual 20 pages 30.11 Kb

300 specifications

The Emerson 300 is a robust and versatile solution designed to enhance industrial automation and control processes. This advanced platform is part of Emerson's comprehensive portfolio, bringing a suite of features and technologies that cater to various industries, including oil and gas, manufacturing, and energy management.

One of the standout features of the Emerson 300 is its scalability. The system is built to grow with your business, allowing users to start with a small setup and expand it seamlessly as operational needs evolve. This flexibility makes the Emerson 300 an economical choice for companies of all sizes, as it can accommodate increased workloads without significant upfront investment in additional hardware.

The Emerson 300 employs cutting-edge communication technologies, including Ethernet and various fieldbus systems, ensuring effortless integration with existing infrastructure. This connectivity enhances data exchange between devices, enabling real-time monitoring and control. The platform supports a variety of protocols, making it compatible with a wide range of industrial sensors and actuators.

Enhanced data analytics capabilities are another hallmark of the Emerson 300. The device leverages sophisticated algorithms to analyze performance metrics, predict equipment failures, and optimize operations. This proactive approach not only reduces downtime but also maximizes equipment lifespan and efficiency.

Furthermore, the Emerson 300's user interface is designed with operator ergonomics in mind. A customizable dashboard provides key performance indicators at a glance, empowering operators to make quick, informed decisions. The intuitive design minimizes training requirements and promotes user adoption, fostering a culture of safety and productivity in the workplace.

In terms of security, the Emerson 300 incorporates advanced cybersecurity measures, protecting critical data from unauthorized access and cyber threats. Regular updates and patches ensure that the system remains resilient against the evolving landscape of industrial cybersecurity challenges.

Overall, the Emerson 300 is a powerful industrial automation solution that seamlessly integrates advanced technologies, robust scalability, and user-friendly design. Its adaptability to various industrial environments paired with its enhanced analytics and security features make it a valuable asset for companies looking to optimize their operations and stay competitive in today's rapidly changing marketplace. Whether it's monitoring real-time data, managing complex processes, or ensuring system security, the Emerson 300 stands out as a reliable partner in industrial automation.