Installation -- Continued
Grounding the Media Converter
The
The electrical conducting path from the
•Flow via the grounding lugs to the common bonding network (CBN) for telecom installations, or to an alternative approved grounding system (if required) for
•Be of sufficiently low impedance to conduct fault currents likely to be imposed on the media converter, and
•Enable proper operation of any
The conductor must be fastened to the grounding lugs with the enclosed anti- rotation
Lug nuts (included)
Star washer (included)
(not included)
Grounding lugs | 12 AWG copper wire |
(not included) |
spacing
To properly ground the CPSMC0100-210 single-slot chassis:
1.Obtain one (1) grounding conductor (12 AWG copper wire gauge or larger) with a
2.Attach the grounding conductor to the converter by placing the
Technical Specifications
For use with Transition Networks Model
Note: The maximum power delivery capacity for the chassis slot is 12 Watts.
Compliance | EN55022; CISPR 22; Class A & B; CE Mark | |
Dimensions | 6.086 x 5.875 x 1.5 in (155 x 149 x 38 mm) | |
Weight | 1.6 lbs. (0.7 kg) Approximately | |
Power Supply | 12VDC, 1.25 A (maximum) | |
MTBF | 49,888 hours (MIL217F2 V5.0) | |
| 133,257 hours (Bellcore7 V5.0) | |
Environment | Tmra*: | 0 to 50°C (32 to 122° F ) |
| Storage Temp: | |
| Humidity: | 5 to 95%, non condensing |
| Altitude: | 0 to 10,000 feet |
Warranty | Lifetime |
|
*Manufacturer’s rated ambient temperature.
The information contained in this user’s guide is subject to change. For the most
3. Attach the opposite end of the grounding conductor to the common bonding network (CBN) for telecom, or to earth ground (if required) for non- telecom installations.