The controller shall have two sets of Form “C” contacts for Pump Running, Phase Reversal, and Power/Phase Failure, and one set of Form “C” contacts for Trouble. The Trouble contacts shall be activated by the following conditions: Invalid Configuration Memory, Emergency Manual Start, Pump Running, Phase Failure, Phase Reversal, Overload, Locked Rotor,
The controller shall be equipped with LXi intelligent fire pump control system logic. All firmware shall be
The digital pressure readings and settings shall be displayed on the LXi LCD mounted on the enclosure flange. The LCD screen shall be 4 x 20 (4 lines of 20 characters) per screen, and the screens may be scrolled to give a total of 320 characters. The real time display shall give simultaneous
The event alarm caches shall be compartmentalized, and no compartment shall
1.Events that have occurred during a pump idle period
2.Events that occurred during the last start period
3.Events that occurred during the last run period
4.Events that occurred during the last stop period.
The LED displays shall be mounted on the enclosure flange and have an LED for the following:
Power Available | Fail to Start | Lockout On |
Low Suction | Phase Reversal | Run Timer On |
Pump Start Delay On | Shorted SCR | Pump Running |
Locked Rotor | Overload | Overtemp SCR |
Pressure Switch Start | Local Manual Start | Remote Start |
Emergency Manual Start | Local Manual Stop | Start Timer/Accelerate |
LED’s shall be
Programming of the LXi logic shall be from the touch pad mounted on the enclosure flange. Programming shall be password protected so that only authorized personnel can change the logic functions. The fire pump controller shall be Model LXi 1100 equipped with LXi Logic as manufactured by Hubbell Industrial Controls, Inc.