Tripp Lite Audio/Video Pure Sine Wave UPS System owner manual On FAULT, 50% Flashing Line

Page 10

Troubleshooting

The UPS’s control panel lights will turn on in the sequences below to signal that the UPS is having operational difficulties.

Lights (On/Flashing) and Condition

Solution

On: REPLACE BATT

Let the UPS system charge for at least 12 hours

Condition: Replace Battery

and perform a self test using the "ON/Test

 

Switch" as described on page 6. If the light

 

continues to stay on, contact Tripp Lite for service.

 

 

On: BATT LOW, ON BATT

Prepare for imminent UPS shutdown.

Condition: Battery Low

 

 

 

On: BYPASS, LINE, LOAD, OVERLOAD

Reduce the load the UPS supports.

Condition: On Bypass due to Overload

 

 

 

Flashing: OVERLOAD

Remove the cause of the short circuit

Condition: Short Circuit

from the UPS output.

 

 

On: FAULT

Check the utility line for wiring problems such as

Condition: Wiring Fault

reversed line and neutral or a missing ground.

 

 

On: FAULT, 100%

Restart the UPS. If the problem persists,

Condition: Battery Voltage too High

contact Tripp Lite for repairs.

 

 

On: FAULT, BYPASS, LINE, 50%

Restart the UPS. If the problem persists,

Condition: On Bypass due to

contact Tripp Lite for repairs.

High Output Voltage

 

 

 

On: FAULT, BYPASS, LINE

Restart the UPS. If the problem persists,

Flashing: 50%

contact Tripp Lite for repairs.

Condition: On Bypass due to

 

Low Output Voltage

 

On: FAULT, BYPASS, LINE, 25%

Condition: On Bypass due to High Bus Voltage

Restart the UPS. If the problem persists, contact Tripp Lite for repairs.

On: FAULT, BYPASS, LINE

Flashing: 25%

Condition: On Bypass due to Low Bus Voltage

Restart the UPS. If the problem persists, contact Tripp Lite for repairs.

On: BYPASS, LINE

Check the UPS to be sure that there is

Flashing: FAULT

adequate space for air to circulate near

Condition: On Bypass due to High

the vents and that the fan is working

Internal Temperature

properly. Restart the UPS.

 

 

Flashing: LINE

This indicates that utility power is too high or low

Condition: Input Abnormal

for the UPS to operate in BYPASS mode, so if an

 

inverter failure occurs, the UPS will deliver no output.

On: FAULT, 50%

Flashing: LINE

Condition: No Output due to High Output Voltage and Abnormal Input

Restart the UPS. If the problem persists, contact Tripp Lite for repairs.

On: FAULT

Flashing: LINE, 50%

Condition: No Output due to Low Output Voltage and Abnormal Input

Restart the UPS. If the problem persists, contact Tripp Lite for repairs.

10

Image 10
Contents Registration WarrantyTh Street Chicago, IL 60609 USA Important Safety Instructions Rack Mounting Tower MountingConnection and Start-Up Optional ConnectionsUSB and RS-232 Serial Communications Front Panel Switches Front Panel Indicator LightsBasic Operation Front Panel Indicator Lights Rear Panel Communications On FAULT, 50% Flashing Line On Fault Flashing LINE, 50%Procedure Service StorageCondiciones para la Póliza De Garantía en México