4 post installation hardware included, Optional 2POSTRMKITHD enables 2 post rack installation
Single line TEL / Network surge suppression
Electronic bypass maintains utility output during a variety of UPS fault conditions
Battery independent restart ensures automatic UPS
Frequency regulation / conversion mode offers
Included PowerAlert UPS monitoring software
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
Output kVA capacity (kVA)
Output Watt Capacity (watts)
Output kW capacity
Output power factor
Output Capacity Details
3000
3
2700
2.7
0.9
ON LINE MODE: Maximum output capacity ratings are reduced for some nominal voltage settings (127/120V 2700 watts / 115V 2430 watts / 110V 2295 watts / 100V 2160 watts). FREQUENCY REGULATION / CONVERSION MODE: Maximum output ratings are reduced in frequency regulation / conversion mode (127/120V 1890 watts / 115V 1701 watts / 110V 1606 watts / 100V 1512 watts).
Crest Factor
Nominal Output
Voltage(s)
Supported
3:1
100V; 110V; 115V; 120V; 127V
Nominal Voltage details
Frequency compatibility
Frequency compatibility details
120V
50/60 Hz
ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output matches input frequency when
Output voltage regulation (line mode)
+/- 2%
Output voltage regulation (Economy line mode)
+/- 10%
Output voltage regulation (Battery mode)
+/- 3%
4