Tripp Lite SU2200RTXL2UA Environmental, Communications, Line / Battery Transfer, Special Features

Page 4

Shipping weight (lbs)

Shipping weight (kg)

Shipping Dimensions (HWD/in)

57.3

26

9.75 x 20.25 x 24

Shipping Dimensions (HWD/cm)

24.8 x 51.4 x 61

Unit weight (lbs)

47.4

 

 

Unit weight (kg)

21.5

 

 

Unit Dimensions

3.5 x 17.5 x 19

(HWD/in)

 

 

 

Unit Dimensions

8.9 x 44.4 x 48.3

(HWD/cm)

 

 

 

Material of

Steel

construction

 

 

 

Form factors

Rack (2U)

supported

 

 

 

Cooling method

Built-in cooling fan

 

 

Battery Access

User replaceable, hot swap battery replacement supported via front access panel

 

 

ENVIRONMENTAL

 

Relative Humidity

0 to 95%, non-condensing

 

 

Storage

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Temperature

 

 

 

Operating

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Temperature

 

 

 

Line mode BTU/hr.

812.9 BTU/hr. (worst case)

(Max.)

 

 

 

Battery mode

885.6 BTU/hr. (worst case)

BTU/hr. (Max.)

 

 

 

COMMUNICATIONS

 

Network

Includes USB and DB9 serial ports. Built-in DB9 port offers both enhanced RS-232 enabled monitoring data, plus contact

monitoring port

closure monitoring ability. HID-compliant USB interface enables integration with built-in power management and auto

 

shutdown features of Windows and Mac OS X.

 

 

Software and

Yes, includes PowerAlert software CD-ROM and complete cabling

cabling included

 

 

 

SNMP compatibility

Yes, includes slot for optional SNMPWEBCARD accessory (#SNMPWEBCARD)

 

 

WatchDog

Yes, compatible with Tripp Lite's Watchdog system service to restore operation to locked equipment through soft reboot

compatibility

of application / OS or hard power off/on reboot of connected equipmentideal for unattended kiosk applications

 

 

LINE / BATTERY TRANSFER

Transfer time from line power to battery mode

Low voltage transfer to battery power

Zero, online UPS continuously converts incoming AC to DC, then back to AC. When commercial power is interrupted, UPS maintains continuous output from battery reserves with absolutely no disruption in output AC power.

Maintains continuous operation during undervoltages as low as 65V (80V at load levels over 70%). Below this switchover point, output is supported from battery derived AC power.

High voltage

Maintains continuous operation without using battery power during overvoltages to 138V. Above this point, output is

transfer to battery

supported from battery derived AC power.

power

 

 

 

SPECIAL FEATURES

 

EPO port

Supports "Emergency Power Off" via dedicated built-in EPO jack

 

 

Image 4
Contents Description HighlightsUPS Features SpecificationsSystem Overview OutputBattery Leds Alarms & SwitchesInput Voltage RegulationLine / Battery Transfer Special FeaturesEnvironmental CommunicationsRelated Items WarrantyCertifications Tripp Lite. All Rights Reserved