Accepts input voltages between 156 and 276, regulating output within 2% of selectable 208/240 and 120V AC output
Standard included 3U battery pack provides 20 minutes runtime at half load (3000VA) and 8 minutes at full load (6000VA) Expandable runtime is supported with optional BP240V10RT3U;
Highly efficient operation in optional economy mode significantly reduces BTU heat output and operating energy costs
PowerAlert monitoring software offers detailed site power and UPS updates with support for safe
Includes Free PowerAlert monitoring software packages; PowerAlert LOCAL for desktops and small business networks, PowerAlert NSA (Network Shutdown Agent) for larger networks and PowerAlert NMS (Network Management System) for monitoring up to 250
Supports detailed monitoring of equipment load levels,
Optional SNMPWEBCARD offers communications and control via secure remote web and network interfaces
Optional RELAYIOCARD supports six configurable hard contact closure outputs for custom event notification
Supports Emergency Power Off (EPO) via
Included rail kit supports 9U 19 inch rackmount installation in 4 post racks
Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks
Front panel LED's and LCD readout with scroll controls and supports visual monitoring of all major UPS functions and advanced UPS settings for nominal voltage selection, economy mode, and other operational parameters
LED / LCD display panel rotates for viewing in rackmount or tower configurations
External battery packs are field replaceable and hot swappable
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
Output kVA capacity (kVA)
Output Watt Capacity (watts)
Output kW capacity
Output power factor
Crest Factor
Nominal Output Voltage(s) Supported
Frequency compatibility
Frequency compatibility details
Output voltage regulation (line mode)
Output voltage regulation (Economy line mode)
6000
6
4200
4.2
0.7
3:1
120V; 208V; 240V
50 / 60 Hz
Output frequency matches input nominal on startup
+/- 2%
+/- 10%
Output voltage regulation (Battery mode)
+/- 2%