Tripp Lite SU5000RT3U warranty Specifications, System Overview, Output, Input, Battery

Page 2

True online, double-conversion UPS provides pure, full-time sine wave AC output free of surges, voltage fluctuations and line noise

5000VA/3500 watt output power capacity with dual high/low voltage output compatible with 200-240V and 120V applications simultaneously

3U power module, 2U transformer module and 2U battery pack installs in any 19 inch rack enclosure using only 7 rack spaces

Dual conversion UPS actively converts raw input from AC to DC, then back to perfect sine wave AC output with enhanced protection from harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types

Provides perfectly regulated, sine wave output power free of line noise, transient surges and frequency variation for the most efficient operation of critical servers, networking and telecommunications equipment

Accepts input voltages between 156 and 276, regulating output within 2% of 208 - plus 120V nominal voltage

Supports connected equipment during blackouts for 20/8 minutes at half/full load levels, runtime is further expandable with optional external battery packs

Network interfaces support simultaneous communications via 2 DB9 ports and SNMPWEBCARD slot

Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number of additional servers over IP

Communications ports support on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery capacity, AC line frequency, timed inverter shutoff, activate self-test and output power control

Built-in Emergency Power Off (EPO) interface with cable

Includes 17 built-in output receptacles (3 L6-30R w/one L6-30R used for transformer connection, 2 L6-20R, 12 NEMA 5-15/20R)

L6-30P input plug-in connection

Front panel LEDs and LCD readout with scroll button enables visual confirmation of all major UPS functions and current site electrical conditions

Front panel switches enable power on/off control, self-test and alarm cancel functions

Included adjustable mounting rails support installation in 4 post 19 inch rack enclosures, optional 2POSTRMKITWM supports 2 post rackmount installation

UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user is required Fault-tolerant auto-bypass maintains continuous utility output to connected equipment, even in cases where the UPS is overloaded or suffers an internal failure that requires service

2 year manufacturer's product warranty, $250,000 Ultimate Lifetime Insurance (USA & Canada only)

Specifications

SYSTEM OVERVIEW

Voltage compatibility

208V AC

 

 

Frequency

50/60Hz

compatibility

 

 

 

OUTPUT

 

Output VA

5000

 

 

Output watts

3500

 

 

Output nominal

208V & 120V AC

voltage

 

 

 

Output voltage

Maintains pure sine wave output at all times, regulated within 2% of selected nominal output voltage, less than 5% total

regulation

harmonic distortion

 

 

Output frequency

Regulates line frequency to 50/60Hz +/- 0.05Hz

regulation

 

 

 

Outlet quantity / type

2 NEMA L6-30R, 2 NEMA L6-20R, 12 NEMA 5-15/20R

 

 

Overload protection

Resettable circuit breaker

 

 

INPUT

 

Maximum input amps

24A 208V / 21A 240V

 

 

Input connection type

NEMA L6-30P

 

 

Input cord length

10 ft / 3 m

 

 

Recommended

30A

Electrical Service

 

 

 

BATTERY

 

Full load runtime

8 minutes (5000VA / 3500 watts)

Half load runtime

20 minutes (2500VA / 1750 watts)

Image 2
Contents Description FeaturesHighlights System Overview SpecificationsBattery OutputPhysical Leds Alarms & SwitchesSurge / Noise Suppression EnvironmentalWarranty Line / Battery TransferSpecial Features Related ItemsTower Stands Start-Up/Warranty ServicesSurge Protectors