Tripp Lite SMART700USB warranty Specifications, Output, Input, Battery, Voltage Regulation

Page 2

USB port enables unattended shutdown without data loss during extended power failures, includes USB cable

Built-in USB port supports on battery, low battery, power restored, AC line voltage, DC battery voltage and battery capacity messaging; interface supports timed inverter shutoff after unattended shutdown, activate self-test and 10 second reboot of connected equipment

PowerAlert UPS monitoring and unattended shutdown software available via free download from www.tripplite.com

Supports Tripp Lite's WatchDog software application to restore unresponsive programs by automatically restarting them and rebooting completely locked computers by automatically switching UPS power off and back on again (part #75-0071)

Built-in dataline suppression jacks protect a single dialup phone/DSL line or network ethernet line connection

Built-in audible alarm and 4 front panel LEDs indicate UPS system and line power status

700VA/450 watt power handling ability supports a variety of computer, internetworking, telecom and consumer electronics equipment

Supports battery replacement via built-in access panel

Compatible with 120V/60Hz applications for USA, Canada, Mexico and more

2 year manufacturers warranty

$200,000 connected equipment insurance (USA & Canada Only)

Specifications

OUTPUT

Frequency compatibility

Output VA

Output watts

Output nominal voltage

Output voltage regulation

Output frequency regulation

Outlet quantity / type

INPUT

60 Hz

700

450

120V AC

BATTERY MODE: PWM sine wave 120V +/-5%

LINE MODE: Passes line frequency of 60Hz +/-10%

BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz

6 NEMA 5-15R output receptacles (3 with UPS and surge suppression / 3 with surge suppression only)

UPS Input cord length (ft.)

Recommended Electrical Service

Maximum Input

Amps (A)

Input connection type

Voltage compatibility (VAC)

BATTERY

6 ft., 16 gauge

15A 120V

10

NEMA 5-15P

120

DC system voltage (VDC)

Battery Access

Full load runtime

Half load runtime

Typical battery lifespan

12

Battery access door allows user replacement of UPS batteries

5 minutes (700VA)

17 minutes (350VA)

3-6 years, depending on usage

Battery recharge rate

2-4 hours to 90%

VOLTAGE REGULATION

Image 2
Contents Description FeaturesHighlights Output SpecificationsBattery InputPhysical Leds Alarms & SwitchesSurge / Noise Suppression EnvironmentalWarranty Line / Battery TransferSpecial Features Certifications