InFocus 165 owner manual Rating Label, Nameplate, Catalog number

Page 1

Owner’s

Manual

Series 165 Automatic Transfer Switches

rated 100, 200, & 230 amps, single phase, 240 V ac

for automatic 2–wire start generators

DANGER is used in this manual

to warn of risk of electrical shock

from high voltages capable of

causing shock, burns, or death.

!

WARNING is used in this manual to warn of possible personal injury.

!

CAUTION is used in this manual to warn

of possible equipment damage.

Installation should be performed by a licensed electrician and in accordance with the National Electrical Code (NEC) and all local electrical code requirements. Read and understand all instructions before installing, servicing, or operating. Failure to do so could result in serious

ASCO Series 165 Automatic Transfer Switches are Listed under the Underwriter’s Laboratories Standard for Transfer Switch Equipment, UL–1008. They are intended for use only in optional standby systems in accordance with the National Electrical Code, NEC/NFPA 70, Article 702. This ATS is for use with 2–wire automatic start generators only.

Refer to Application Information 381339–219 to confirm that you have selected the appropriate product for the intended installation.

Rating Label

Each Automatic Transfer Switch (ATS) has rating labels to define the loads and fault current withstand/ closing ratings. Refer to those label on the Transfer Switch for specific values.

!

INJURY or SWITCH DAMAGE Do not exceed the rating label values; it can cause personal in- jury or serious switch damage.

personal injuries or property damage.

Nameplate

The Transfer Switch nameplate includes data for each specific ASCO Series 165 ATS. Use the switch only within the limits shown on this nameplate. A typical Catalog Number is also shown below with its elements explained:

Series

165

Automatic Transfer Switch for use on Standby Systems Cat No 165A2200F3C

Ser No 123456

200 A BOM 999999

240 V 60 Hz

Catalog number

product

165 A 2 200 F

 

designation

 

neutral

A = solid neutral

poles

2 = 2 lines

ampere rating

100, 200, or 230 amps

3 C

enclosure C = Type 1 F = Type 3R

control group code 3 = automatic

voltage code F = 240 V AC

50 Hanover Road, Florham Park, New Jersey 07932–1591 USA

381333–163 C

1 800 937–2726 (ASCO), for service call 1 800 800–2726 (ASCO) www.asco.com

ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3 telephone 519 758–8450, fax 519 758–0876, for service call 1 888 234–2726 (ASCO) www.asco.ca

Image 1
Contents Nameplate Rating LabelCatalog number Table of Contents Introduction SpecificationsCable Connections see wiring diagram InstallationElectrical Line Connections Cable Spacers 200 and 230 amp. unitsVoltage Checks Manual OperationElectrical Operation Operation Indicator LightsUtility Failure Push ButtonsAutomatic Generator Exerciser Manual Generator TestingProblem TroubleshootingElectrocution Flash Hazard