Configuring the Rack ATS
Configuring sensitivity
The sensitivity setting controls how tolerant the Rack ATS is of fluctuations in power before it switches to the secondary power source. Configure the sensitivity range for your Rack ATS using the Switch Configuration menu, which can be found by selecting the Unit tab and the Configuration menu in the left navigation menu. When sensitivity is set to Low, the Rack ATS waits 4 ms before switching to the alternate power source when there is a disturbance in the power supply. When sensitivity is set to High, the Rack ATS waits 2 ms before transferring power. The default setting is High.
Configuring voltage transfer range
The voltage transfer range determines the acceptable RMS voltages for the Rack ATS. When voltage moves outside the specified range, the Rack ATS switches to the secondary power source. Configure the voltage transfer range using the Switch Configuration menu. The Rack ATS can be set to Narrow, Medium, or Wide voltage ranges, depending on the power conditions of your system.
Note: The default setting of the voltage range is Medium.
APC Part | Nominal Voltage | Narrow | Medium | Wide |
Number | ||||
AP7721 | 230 Vac | ±16 | ±23 | ±30 |
AP7722A | 230 Vac | ±16 | ±23 | ±30 |
AP7723 | 230 Vac | ±16 | ±23 | ±30 |
AP7724 | 230 Vac | ±16 | ±23 | ±30 |
AP7730 | ±15 | ±20 | ±25 | |
AP7732 | ±15 | ±20 | ±25 | |
AP7750A | 120 Vac | ±8 | ±12 | ±20 |
AP7752 | 120 Vac | ±8 | ±12 | ±20 |
AP7752J | 100 Vac | ±5 | ±10 | ±15 |
AP7753 | 120 Vac | ±8 | ±12 | ±20 |