APC AP9620 manual Ups, Usb, Or Function, Smartslot Card Installed

Page 2

UPS Operations with SmartSlot card. The table documents how UPS devices operate with the card.

 

 

UPS:

UPS operational issue

Smart Serial: DB-9F smart signaling interface

 

Types of Interface Simple: Simple Signal interface via DB-9F

USB:

USB-B port on the card.

 

INTER

COMMAND

 

HISTORIC

OPERATION WITH LEGACY COMMUNICATIONS

 

 

-FACE

OR FUNCTION

 

OPERATION

 

SMARTSLOT CARD INSTALLED

 

1

Simple

Remote On

 

Not always supported. Some UPS devices

Remote On is enabled when AC utility power is on OR

 

 

 

 

 

allowed starting with the Remote On signal

when AC power has been off for less than 10 minutes.

 

 

 

 

when AC utility power was off.

 

 

 

2

UPS

On button operation

 

UPS turned on immediately.

UPS turns on after the configured Turn on Delay. The

 

 

 

 

 

 

default setting is "0" (zero) - immediately turn on.

3

UPS

Switched Outlets

 

Were not supported.

Where relevant, switched outlet operation is disabled: all

 

 

 

 

 

 

the UPS outlets function simultaneously. (The Main

 

 

 

 

 

Outlet Group might turn on slightly before, and turn off

 

 

 

 

 

slightly after, the other outlets). Switched outlet-related

 

 

 

 

 

LCD menu screens are not accessible.

4

UPS

RJ-45 comms port

 

Was not supported.

Disabled.

 

 

5

UPS

USB comms port

 

Differed, depending on setup.

Disabled.

 

 

6

UPS

Self-test Operation

 

Could always be initiated.

1. A self-test is enabled on extended-run UPS devices

 

 

 

 

 

 

with more than 8 hours runtime. 2. A UPS might prevent

 

 

 

 

 

a self-test if the battery charge is < 70%.

7

UPS

Runtime Calibration

 

A runtime calibration could be initiated,

Two conditions must be met: 1. The battery charge must

 

 

 

 

 

regardless of load and battery charge.

be 100%. 2. The load must be => 10% of the UPS rating.

8

Smart

Test lights and

 

The UPS beeped for 1.5 seconds

Beep operation is determined by the UPS; some newer

 

 

Serial

beeper

 

 

UPS devices have a 5 second beep.

9

Smart

Simulate Power

 

The UPS operated momentarily on battery.

The UPS does not go to battery operation, but

 

 

Serial

Failure

 

 

temporarily remembers this command (in order to enable

 

 

 

 

 

the Shutdown on Battery command).

10

Smart

Establishment of

 

Serial communications had to be re-

No change.

 

 

Serial

Communications

 

established each time the UPS turns on.

 

 

 

11

Smart

Minimum battery

 

After a complete discharge of batteries in an

The UPS reads the value as a %, and restarts as follows:

 

 

Serial

capacity to restart

 

outage, the UPS restarted when the battery

0%—an immediate restart; 15%—with runtime of 90

 

 

 

 

charge reached this value.

secs.; 30%—with runtime of 180 secs.; up to a

 

 

 

 

 

maximum 90%—restarts with runtime of 240 secs.

12

Smart

Battery Replacement

Any 8 characters were supported.

The date format must be mm-dd-yy, with any separating

 

 

Serial

Date

 

 

character (“-” here) supported. Dates prior to the UPS

 

 

 

 

 

manufacture date are not accepted.

13

Smart

Alarm delay after

 

On some UPS devices you could set the

UPS devices can enable, disable or mute the alarm. If

 

 

Serial

line fail

 

beeper to sound after being on battery for 30

beeping at low battery or on battery is selected, the alarm

 

 

 

 

secs, or at low battery. All UPS devices

is disabled, but the setting is displayed on the LCD

 

 

 

 

could mute and disable the beeper.

screen.

 

 

14

Smart

UPS Model

 

Returned the device name, e.g. Smart-UPS

Returns the closest equivalent historical name, which

 

 

Serial/

 

 

750VA

might be different from the name displayed on the LCD

 

USB

 

 

 

screen.

 

 

15

Smart

Nominal Battery

 

Reported the nominal battery voltage of the

The nominal battery voltage is not known so the card

 

 

Serial

Voltage

 

UPS.

“estimates” it and returns 024, 048, or 192; if an estimate

 

 

 

 

 

is impossible, the card reports 024.

 

16

Smart

Upper Transfer

 

 

For SURTD UPS devices, the card displays the

 

Serial

Voltage

 

 

 

 

 

corresponding bypass limit; but the allowable range of

17

Smart

Lower Transfer

 

 

 

 

values is determined by the voltage setting of the UPS.

 

Serial

Voltage

 

 

 

 

 

 

 

 

18

USB

DelayBeforeReboot

 

The Turn Off Delay setting was applied

The Turn Off Delay setting is applied before the UPS is

 

 

 

 

 

before turning the UPS off, the UPS

turned off, the UPS remains off for the time specified,

 

 

 

 

remained off for the time specified, and was

and the Turn On Delay is applied before the UPS is

 

 

 

 

then turned back on immediately.

turned back on.

19

USB

USB communication

Not present on SURTD UPS devices.

Not functional when installed in a SURTD UPS device.

 

Customer support and warranty information is available at the APC Web site, www.apc.com.

© 2010 APC by Schneider Electric. APC, the APC logo, and UPS-link SmartSlot Card are owned by Schneider Electric Industries S.A.S., American Power Conversion Corporation, or their affiliated companies. All other trademarks are property of their respective owners.

990-4208A 8/2010