Powerware 1500 Specifications, Troubleshooting, Service and Support, LED Indicator Table

Page 2

4.5AH, 5AH batteries (350VA, 500VA models)

1

2

3

4

5

6

7

8

9

7AH x 1 battery (700VA models)

 

 

1

2

3

4

5

6

7

8

9

7AH x 2, 9AH x 2 batteries (1000VA, 1500VA models)

1

2

3

4

5

6

7

8

9

Status Indicators

The UPS provides both visual and audible status indicators. Visual indicators consist of three LEDs to represent the following conditions:

On utility power operation On battery power operation UPS fault/alarm

LED Indicator Table

On Utility (AC mode)

Green Lighting

On Battery (Backup mode)

Yellow Lighting

Low Battery

Yellow Flashing

Fault/Output Short

Red Lighting

Overload/Check Battery

Red Flashing

LED Audible Alarm Table

Backup mode

Sounding every 5 seconds

Battery low

Sounding (two beeps) every 5 seconds

Overload

Sounding every 0.5 seconds

Replace battery

Sounding (three beeps) every 30 seconds

Fault or output short circuit

Continuous sounding

Battery over charge

Sounding (three beeps) every 5 seconds

SPECIFICATIONS

Model Numbers

Capacity

PW5110 350 USB

350 VA / 210W

PW5110 500 USB

500 VA / 300W

PW5110 700 USB

700 VA / 420W

PW5110 1000 USB

1000 VA / 600W

PW5110 1500 USB

1500 VA / 900W

Nominal Input Voltage

120Vac

 

 

Nominal Output Voltage

120Vac

 

 

Automatic Voltage Regulation (AVR)

15%

 

 

Frequency

50 / 60 Hz auto sensing

 

 

Outlets

8 Outlets (4 Battery Backup & Surge Protection;

4 Surge Protection only)

 

 

 

Lighting / Surge Protection

320 Joules

 

 

Transfer time to Battery/AC

6ms typical

 

 

Battery Type

Maintenance free lead-acid battery

 

 

 

350 VA: 12V 4.5 Ah

 

500 VA: 12V 5 Ah

Battery Specification

750 VA: 12V 7 Ah

 

1000 VA: (2) 12V 7 Ah

 

1500 VA: (2) 12V 9 Ah

 

 

Typical Backup Time

3 MINUTES MINIMUM AT FULL RATED LOAD

 

 

LAN / Phone / Fax Protection

RJ11/RJ45

 

 

Short Circuit Protection

Circuit Breaker

 

 

Communication Port

USB

 

 

Operation Temperature

0 C~40 C

 

 

Operation Relative Humidity

0 to 95% non-condensing

 

 

Storage Temperature

-15 C~50 C

 

 

 

350 VA: 11.9 pounds / 5.4 kg

Net Weight

500 VA: 12.13 pounds / 5.5 kg

700 VA: 15.21 pounds / 6.9 kg

 

1000 VA: 28 pounds / 12.7kg

 

1500 VA: 29.1 pounds / 13.2 kg

Dimensions (HxWxD)

350 / 500 / 700 VA: 10.6 x 3.4 x 10 in.

1000 / 1500 VA: 10.6 x 3.4 x 15 in.

 

*Due to continuing product improvement programs, specifications are subject to change without notice.

TROUBLESHOOTING

Symptom

Possible Cause

Action to Take

UPS will not turn on

The UPS is not connected

Ensure the UPS is securely

 

to the power source.

connected to an AC outlet.

 

Circuit Breaker has

Reduce the amount of equipment

 

tripped.

plugged into the “Battery Backup &

 

 

Surge Protection” outlets of the

 

 

UPS. Reset the circuit breaker by

 

 

pushing it back in. Switch the UPS

 

 

back on.

UPS is making a

The “Battery Backup &

Turn off the UPS and reduce the

continuous sound and the

Surge Protection” outlets

amount of equipment connected to

“Overload” indicator is on

are overload.

these outlets.

 

 

 

 

 

 

UPS does not provide

The UPS battery is

Charge the battery for 8 hours. The

expected runtime

discharged due to a power

UPS runtime is reduced until the

 

outage and has not

battery is fully charged.

 

recharged.

 

 

Devices plugged into Back

Unplug non-essential equipment

 

up & surge protection

(printers, scanners, etc) from the

 

receptacles exceed the

Battery Backup outlets and plug

 

rated load for the UPS run

into 'Surge Only' outlets

 

time

 

UPS does not power

The UPS circuit breaker

Disconnect non-essential equipment

essential equipment

tripped .

from the UPS. Reset (push in) the

during an outage

 

circuit breaker and switch the UPS on.

 

 

Plug equipment in one-at-a-time. If

 

 

the circuit breaker trips again,

 

 

disconnect the device that caused the

 

 

breaker to trip.

 

The battery has reached

Replace the battery or the battery

 

the end of its life.

module.

 

Equipment plugged into a

Unplug device from 'Surge Only' outlet

 

Surge Only outlet.

and move to a 'Battery Backup outlet.

Red LED Indicator ON

Internal UPS fault.

Contact Technical Support (see

Service and Support below).

 

 

SERVICE AND SUPPORT

For questions and/or problems, please call your local distributor or the

help desk at one of the following telephone numbers and ask for a UPS technical representative.

United States:

1.800.356.5737

Europe, Middle East, and Africa:

+44.17.53.608.700

Asia:

+852.2830.3030

Australia:

+61.3.9706.5022

Please have the following information ready when you call the Help Desk: Model number

Serial number

Version number (if available)

Date of failure or problem

Symptoms of failure or problem

Customer return address and contact information

If repair is required, you will be given a Returned Material Authorization (RMA) Number. This number must appear on the outside of the package and on the Bill of Lading (if applicable). Use the original packaging or

request packaging from the Help Desk or distributor. Units damaged in shipment as a result of improper packaging are not covered under warranty.

A replacement unit will be shipped, freight prepaid for all units under warranty. For additional information please visit us online: www.powerware.com

MA6B411003A(2005/01/25)

Image 2
Contents Indicators Battery Connection Required Before USE Safety InstructionsInstallation and Operation Battery Replacement ProcedureService and Support SpecificationsTroubleshooting LED Indicator Table

1500 specifications

The Powerware 1500 is a renowned uninterruptible power supply (UPS) solution designed to provide critical backup power for various applications. It is particularly popular among businesses and organizations that require reliable and efficient power protection. The Powerware 1500 is engineered with advanced technologies aimed at ensuring the integrity of electronic equipment, reducing downtime, and enhancing overall operational efficiency.

One of the standout features of the Powerware 1500 is its high output capacity of 1500 VA, enabling it to support moderate-sized servers, networking equipment, and telecommunications systems. The UPS is equipped with sine wave output, ensuring compatibility with sensitive electronic devices and minimizing electrical noise that could lead to equipment malfunctions.

Another significant characteristic of the Powerware 1500 is its versatile design. It includes multiple outlets that allow for simultaneous connection of various devices. This multi-outlet setup is essential for users who need to protect multiple pieces of equipment from power disturbances. Additionally, the device supports hot-swappable batteries, which means users can replace the battery without interrupting the connected equipment. This feature is critical for maintaining operations during battery maintenance.

The Powerware 1500 utilizes advanced battery management technology, which maximizes the battery's lifespan and performance. The UPS features intelligent temperature-compensated charging that adjusts the charging voltage based on the surrounding temperature, thus prolonging battery life. Furthermore, the unit includes a user-friendly LCD interface that provides real-time data on power status, battery condition, and load capacity, making it easier for users to monitor the system at a glance.

The Powerware 1500 also incorporates a range of protective technologies. It comes with overload protection, short-circuit protection, and automatic voltage regulation (AVR) to ensure stable output even during voltage fluctuations. This is particularly advantageous in regions where power quality is inconsistent.

In summary, the Powerware 1500 combines robust technical features, user-friendly design, and reliable power management technologies, making it an ideal choice for businesses seeking dependable power protection. Its advanced features not only enhance performance but also safeguard critical equipment, ensuring seamless operations even in the face of electrical disturbances.