Omega Engineering PSW2000 manual Product Description, Starting operations

Page 3

PSW2000.qxp 6/12/2008 10:37 AM Page cov-5

1. Product Description

Dimensions (in mm)

PSW3000

Intended Applications

-The dual pressure switch monitors system pressures and has up to two switching outputs and one analog output.

-According to DESINA￿ standard

-The instruments must only be installed in systems where the maximum pressure Pmax is not exceeded (according to the values on the type label).

-Attention: This device is not designed to be used as the only safety relevant element in pressurized systems according PED 97/23/RC

2. Starting operations

Only install or uninstall the device when depressurized!

-Mount the pressure switch from bottom to the fitting with a wrench hex 36 (1/4 ) resp. 19 with 45 Nm torque.

-Electrical connection depends on the type of pressure switch (see type label) according to the chart below.

Electrical connections

Plug

Model with 1

Model with 2

Model with 1 switching

M 12 x 1,

switching output

switching outputs

output and 1 analog output

4-pin

 

(DESINA￿)

 

 

 

 

 

Pin 1

(15...32 V DC)

(15...32 V DC)

(15...32 V DC)

Pin 2

-

SP2 (0,5 A max.)

analog

Pin 3

0 V

0 V

0 V

Pin 4

SP1 (0,5 A max.)

SP1 (0,5 A max.)

SP1 (0,5 A max.)

3

Image 3
Contents User’ sGuide Servicing North America Only install or uninstall the device when depressurized Product DescriptionStarting operations Dialog item Value Description Only models with 2nd switching contactDialog item Value Only models with analog output Description Operation ProgrammingDesina conformity WARRANTY/DISCLAIMER Shop online at omega.com